olympia electronics Tuv BS-531/1 Manual

Sounder with beacon for fire detection panel

Advertisement

ΒS-531/1
SOUNDER WITH BEACON FOR FIRE DETECTION PANEL
OPERATION VOLTAGE
MAXIMUM CONSUMPTION
MAXIMUM SOUND OUTPUT in1m
BEACON
ΤYPE OF APPLICATION ENVIRONMENT
MOUNTING
COVERAGE (y)
MOUNTING HEIGHT (x)
COVERAGE VOLUME CODE
COVERAGE VOLUME
FLASH RATE
FLASH COLOUR
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIAL
EXTERNAL DIMENSIONS
TYPICAL WEIGHT
GUARANTEE
GENERAL
This device is Visual Alarm Devices (VAD)
for fire detection panels that offer a strong
sound output and an optical warning with a
beacon. The strong sound and the optical
warning beacon cover many square metres.
It features two inputs (N1, N2) for the
production of two different sounds.
device can co-operate with any fire detection
panel (BSR-2104, BSR-2114, BS-1632, BS-
1634, BS-1636, BS-636).

Installation and Connection

1. First, remove the retaining screw, place a
flat blade screwdriver in the holes of the
plastic hooks and remove the plastic cover
(Image 1 on page 2).
2. Remove carefully the beacon connector
(Image 2 on page 2).
3. Use the supplied mounting parts to install
the siren's base at a height of 2.4 metres
from the floor (figure 1 on page 2). Place the
plastic plugs and fasten the screws to the
mounting holes. Attention!! Make sure that the
siren's base is installed upwards as shown in
figure on page 4.
4. Place the caps and make a hole in the
center using a small screwdriver. Pass
Page 1 from 5
All manuals and user guides at all-guides.com
ΤΕCHNICAL CHARACTERISTICS
EN 54-3: 2001 +Α1:2002 +Α2:2006, EN 54-23: 2010
Thank you for your trust in our products
Olympia Electronics - European manufacturer
This
21-28V DC
1.2W
94dB (sound effect 1)
1 Power LED
Τype Α
Wall
6 m around the siren at an angle of 180°
2.4m max
W-2.4-6
86.4m³ (max)
1 Hz (Switchable to 0.5 Hz)
Red
IP42C
0 to 60 C
Up to 95%
Bayblend FR3010, transparent polycarbonate
141 x 141 x 100 mm
230gr.
2 years
through the caps the cables to connect the
device.
5. The (+N1 or the +N2) terminal block is
connected to the (+) output of Alarm-1 or
Alarm-2 of the panel and the (-) of the
terminal block is connected to the (-) output of
Alarm-1 or Alarm-2 of the panel. Accordingly
connect in parallel all the sirens. (The
maximum number of sirens depends on the
type of the panel).
6. To select various sound effects use the
dipswitch 1, 2 and 3 and choose the diserable
sound effect, according to tables 2 and 3 on
page 3.
7. For LED effect variation use the dipswitch
4 (Table 1) on page 2. On the last siren of the
line, we must connect in parallel with its power
cables, the terminal resistor that was removed
from the alarm contacts of the panel.
8. Reinstall the beacon connector (step 2).
Refit the plastic cover until the plastic hooks
are securely attached (step 1) and fasten the
retaining screw (torque 0.6Nm). Attention!!
Make sure that the siren's cover is installed in
the correct orientation.
9. Test the device after installation.
o
921531007_09_008

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Tuv BS-531/1 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for olympia electronics Tuv BS-531/1

  • Page 1 TYPICAL WEIGHT 230gr. 2 years GUARANTEE Thank you for your trust in our products Olympia Electronics - European manufacturer GENERAL through the caps the cables to connect the This device is Visual Alarm Devices (VAD) device. for fire detection panels that offer a strong 5.
  • Page 2 All manuals and user guides at all-guides.com Image 2 Image 1 2 3 4 D i p s w i t c h TO FIRE s i r e n a n d DETECTION b e a c o n Image 3 selections PANEL...
  • Page 3 All manuals and user guides at all-guides.com Page 3 from 5 921531007_09_008...
  • Page 4 Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or not the buyer the transportation cost.
  • Page 5 All manuals and user guides at all-guides.com Figure which shows the correct positioning of the base Horizontal line parallel with the ceiling Wall hole diameter 6mm Page 5 from 5 921531007_09_008...

Table of Contents