Advertisement

Custom Enclosures for OB Burners – OB 24/36/48/72/96 (Must be Non-combustible)
Multiple burners can be connected together in series. When connecting burners together, add
lengths of burners (24", 36", 48", 72", 96") plus 1/2" for total opening length (e.g. 24" + 72" +
24" + 1/2" = 120-1/2").
NOTE: Flame height will be noticeably higher on OB48 burners. This can be manually adjusted.
ENCLOSURES MUST BE NON-COMBUSTIBLE. Enclosures shown are suggestions only. Refer to
Air Openings Required in Custom Enclosures.
the Chart below for
For propane installations see Enclosures for LP (Propane) Gas Supply Systems.
Other Considerations: Gas line Access, GFCI Receptacle (Not Provided). Refer to Local Codes.
NOTE: All Gas Controls and connections must be readily removable, supported, and accessible.
A Wind Guard is recommended.
Refer to Chart for
Required Air Openings.
END VIEW OF OB BURNERS
Remove and discard Ends
when connecting Burners.
Universal Valve Box
Required Openings for Stock
Air Openings Required in Custom Enclosures
-OB24- 35 square inches (e.g. 2 slots 1.5" x 12")
-OB36- 53 square inches (e.g. 2 slots 1.5" x 18")
-OB48- 71 square inches (e.g. 2 slots 1.5" x 24")
-OB72- 106 square inches (e.g. 2 slots 1.5" x 36")
-OB96- 142 square inches (e.g. 2 slots 1.5" x 48")
LED Light
Pan
Burners
OB24 – 5-3/4" x 24-1/2"
OB36 – 5-3/4" x 36-1/2"
OB48 – 5-3/4" x 48-1/2"
OB72 – 5-3/4" x 72-1/2"
OB96 – 5-3/4" x 96-1/2"
Refer to Chart for
Required Air Openings.
Custom
Enclosure with
LED Light Pan –
Right Side View
GFCI Receptacle
(Not Provided)
-Follow Local
Codes-