The zone Biased Differential Current element which compares the actual differential current with the actual trip level “I ” calculated in function of the zone through current I and the bias coefficient R ] + R I operation when Id> ([I Copyright 2010 - Microener...
Page 3
] : 1R = (0.4-1)pU Action starting point of 1R : 1I = (0.5-2)In Per Unit bias coefficient in the area I >[I : 2R =(0.4-1)pU Action starting point of 2R : 2I = (3-8)In Copyright 2010 - Microener...
Page 4
[1I ] [2I ] < [1I ] < I < [2I + 1R(I -[1I > [2I + 1R([2I ]-[1I ]) + 2R(I -[2I BIAS SATURATION : I = 10 In for any I Copyright 2010 - Microener...
Page 5
If not tripped, this button altered. restores the default display. Copyright 2010 - Microener...
Page 6
From ON to OFF, by "ENTER/RESET" push button only if the tripping cause has disappeared. In case of auxiliary power supply failure the status of the leds is recorded and reproduced when power supply is restored. Copyright 2010 - Microener...
Three inputs active when the relevant terminals are shorted are provided: terminals 1 - 2 : For time synchronization terminals 1 - 3 : For trip lock-out terminals 1 - 14 : External trigger for oscillography records Copyright 2010 - Microener...
Page 8
- the validation of the programmed setting - the actuation of test programs - the reset of the default display indication - the reset of signal Leds. e) - Indirect key : Enables access to the programming. Copyright 2010 - Microener...
Page 9
The memory is non-volatile and can be cancelled only with a secret procedure. Display Description dA> xxxx Differential element phase A dB> xxxx Differential element phase B dC> xxxx Differential element phase C Isv xxxx C.Ts. Circuit Supervision Copyright 2010 - Microener...
Page 10
Is – Isv (via digital input B3) 5-10-15 Tsyn Dis m Synchronization time internal 30-60-Dis NodAd 1 Identification number for connection on serial communication bus 1 - 250 The setting Dis indicates that the function is disactivated. Copyright 2010 - Microener...
Page 12
-2-- Un-biased differential element operates relay R2, R3, R4 as programmed --3- Time delayed CT supervision element operates relay R2, R3, R4 as programmed Reset of output relays after tripping is: FRes: Aut. Aut. = Automatic Man. = Manually key Enter /Reset or via serial bus Copyright 2010 - Microener...
If the error message displayed is “E2P Err”, try to program any parameter and then run “W/OTRIP”. If message disappear please check all the parameters. If message remains send the relay to Microelettrica Scientifica (or its local dealer) for repair. Copyright 2010 - Microener...
During power on, time tolerance depends on the on board crystal (+/-50ppm typ, +/-100ppm max. over full temperature range). During power off, time tolerance depends on the RTC’s oscillator (+65 –270 ppm max over full temperature range). Copyright 2010 - Microener...
Tel. (##39) 02 575731 - Fax (##39) 02 57510940 - Telex 351265 MIELIT I http://www.microelettrica.com e-mail : ute@microelettrica.com The performances and the characteristics reported in this manual are not binding and can modified at any moment without notice Copyright 2010 - Microener...