The electronic circuits produced by M.S. are completely safe from electrostatic discharge (8 KV IEC 255.22.2) when housed in their case; withdrawing the modules without proper cautions expose them to the risk of damage. Copyright 2010 - Microener...
The relay can be fitted with two different types of power supply module : 24V(-20%) / 110V(+15%) a.c. 80V(-20%) / 220V(+15%) a.c. a) - b) - 24V(-20%) / 125V(+20%) d.c. 90V(-20%) / 250V(+20%) d.c. Before energising the unit check that supply voltage is within the allowed limits. Copyright 2010 - Microener...
ENTER/RESET the relay has tripped, this button programming mode, allowing any resets the relay and all output or all of the relay’s settings to be contacts. If not tripped, this button altered. restores the default display. Copyright 2010 - Microener...
Leds e,f,h From ON to OFF, automatically when the lit-on cause disappears. In case of auxiliary power supply failure the status of the leds is recorded and reproduced when power supply is restored. Copyright 2010 - Microener...
The relays R1,R2,R3,R4 are normally deenergized (energised on trip): these output relays are user programmable and any of them can be associated to one of the IM30-SA's functions. One relay eventually associated to the instantaneous element of one of the functions, after pick-up normally drops-out as soon as the tripping cause disappears (current below the set trip level).
4 ms). If any internal fault is detected, the display shows a fault message, the Led "PROG/IRF" illuminates and the relay R5 is deenergized. Complete test activated by the keyboard or via the communication bus either with or without tripping of the output relays. Copyright 2010 - Microener...
- Yellow key ENTER/RESET : It allows the validation of the programmed settings - the actuation of test programs - the forcing of the default display indication - the reset of signal Leds. e) - Indirect key : Enables access to the programming. Copyright 2010 - Microener...
As above, earth fault current. IoxxxxOn As above, negative sequence current component xxxxxIn SAxxxxIn Max. current of phase A during the first 100ms. SBxxxxIn As above, phase B. SCxxxxIn As above, phase C. As above, earth fault current. SoxxxxOn Copyright 2010 - Microener...
Io> xxxx Io>>xxxx Trip number of High set earth fault time delayed element [tO>>]. So>xxxxx Trip number of Sensitive earth fault time delayed element [tSo>]. xxxxx Trip number of Negative Sequence O/C time delayed element [tI >]. Copyright 2010 - Microener...
= IEC Very Inverse Curve type B = IEC Extremely Inverse Curve type C (MI) = IEEE Moderate Inverse Curve (SI) = IEEE Short Inverse Curve (VI) = IEEE Very Inverse Curve = IEEE Inverse Curve (EI) = IEEE Extremely Inverse Curve Copyright 2010 - Microener...
Page 14
0.05 - 0.25 0.01 tBO0.05s output relay associated to the Breaker Failure function NodAd 1 Identification number for connection on serial communication bus 1 - 250 The setting Dis indicates that the function is disactivated. Copyright 2010 - Microener...
2tB0 present, it only lasts for the set trip time delay of the function plus an additional time 2xtBO (tBf 2xtBO). As above, for the earth fault elements (tBo Dis) or (tBo 2tBO). tBo 2tB0 Copyright 2010 - Microener...
This is extremely important as discharges eventually tacking place in other parts or components of the board can severely damage the relays or cause damages, not immediately evident to the electronic components. Copyright 2010 - Microener...
Microelettrica Scientifica S.p.A. - 20089 Rozzano (MI) - Italy - Via Alberelle, 56/68 Tel. (##39) 02 575731 - Fax (##39) 02 57510940 http://www.microelettrica.com e-mail : ute@microelettrica.com The performances and the characteristics reported in this manual are not binding and can modified at any moment without notice Copyright 2010 - Microener...
19 of 25 18. WIRING THE SERIAL COMMUNICATION BUS (SCE1309 Rev.0) 19. CHANGE PHASE CURRENT RATED INPUT 1 OR 5A Connector Jumper Rated Input Phase A Current Input Rated Current Phase B Input Rated Current Phase C Copyright 2010 - Microener...
Slide-in the card on the rails provided inside the enclosure. Plug-in the card completely and by pressing the handle to the closed position. Rotate anticlockwise the screws and with the mark in the vertical position (locked). Copyright 2010 - Microener...
Elements blocked by digital input Bf Elements blocked by digital input Bo 2tB0 Reset of phase element blocking input 2tB0 Reset of earth fault element blocking input Commissioning Engineer : Date : Customer Witness : Date : Copyright 2010 - Microener...