The electronic circuits reduced by M.S. are completely safe from electrostatic discharge (8 KV IEC 255.22.2) when housed in their case; withdrawing the modules without proper cautions expose them to the risk of damage. Copyright 2010 - Microener...
The relay can be fitted with two different types of power supply module: 24V(-20%) / 110V(+15%) a.c. 80V(-20%) / 220V(+15%) a.c. a) - b) - 24V(-20%) / 125V(+20%) d.c. 90V(-20%) / 250V(+20%) d.c. Before energizing the unit check that supply voltage is within the allowed limits. Copyright 2010 - Microener...
(see figure) Angles are measured anticlockwise from 0° to 360° with accuracy 2°. Displacement is not measured if current or voltage are null. Copyright 2010 - Microener...
- Time to warm-up from Tp to trip temperature (110%Tn) in function of the current overload (Tx/Tn) (Tp/Tn) (I/[Ib]) (Ip/[Ib]) [Tc]ln [Tc]ln (Tx/Tn) (Tb/Tn) (I/[Ib]) (Ib/[Ib]) (see curves TU0325 §20) Cooling is computed with the same time constant (Tc) as heating. Copyright 2010 - Microener...
Page 8
= (10-1800)s, step 1s [tcs] Cooling time = [tcs] when Cooling only takes places if (see curves TU0312 §19) Copyright 2010 - Microener...
Page 9
= 270°. - Operation zone is that included in the circle having (see figure) : Center on the axle displaced by K2 from the axles’ origin and at distance Diameter = K1 Copyright 2010 - Microener...
Page 10
- Voltage balance (Un +/- 1u) : operates when any phase voltage differs from the rated value more then [1u]% (100 [1u])% (100 [1u])% [Uns] [Uns] - Operation blocked : (Un = Dis) Copyright 2010 - Microener...
Page 11
It operates same as the first element ; the programmable parameters are : - Pick-up level : 2f = (0.05-9.99)Hz, step 0.01Hz - Independent trip time delay : t2f = (0.1-60)s, step 0.1s - Operation mode : (Fn +/- 2f) Copyright 2010 - Microener...
- From ON to OFF, by "ENTER/RESET" push button via serial bus command only if the tripping cause has disappeared. In case of auxiliary power supply failure the status of the leds is recorded and reproduced when power supply is restored. Copyright 2010 - Microener...
This second unit REX-8 is configured (by internal Dip-Switch) to operate the eight relays two by two in parallel (only four user programmable outputs with double number of available contacts) Any of the function featured by the IM3G-VX can be programmed to control up to four out of the sixteen user programmable output relays...
- The relays R5, R DIAG, are not user programmable; they are normally energized and get deenergized on : - internal fault of IM3G-VX - Internal fault of REX-8 R5 - IM3G-VX power supply failure - REX-8 power supply failure R DIAG - during the programming - Interruption/fault on the serial...
4ms). If any internal fault is detected, the display shows a fault message, the Led "PROG/IRF" illuminates and the relay R5 is deenergized. Complete test activated by the keyboard or via the communication bus either with or without tripping of the output relays. Copyright 2010 - Microener...
- Yellow key ENTER/RESET : It allows the validation of the programmed settings - the actuation of test programs - the forcing of the default display indication - the reset of signal Leds. e) - Indirect key : Enables access to the programming. Copyright 2010 - Microener...
As above, phase B As above, phase C ICxx.xIn Negative sequence current as % of generator’s rated current I2xxxx%Ib As above reverse current . (Ir=[(Icos)/Ib] 100) Irxxxx%Ib Active power as % of generator’s rated power Wxxxx%Wb Copyright 2010 - Microener...
Enter the mode "SET DISP", select the menu "SETTINGS" or "FRELAY", scroll information available in the menu by keys "+" or "-". SETTING= values of relay's operation parameters as programmed; FRELAY= output relay associated to the different functions as programmed. Copyright 2010 - Microener...
0.05 - 0.5 - Dis 0.01 (p.u. of Ib) Time multiplier of the I t time-current curve 5 - 80 tcs 10s Cooling time from trip level to the state corresponding to I2=1Is 10 - 1800 Copyright 2010 - Microener...
Page 21
0.05s 0.05 - 0.5 0.01 activation of the output relay associated to the Breaker Failure function The setting Dis indicates that the function is disactivated. Copyright 2010 - Microener...
The blocking input (3) operate on function (Z<) or (Ir>) or (Z<+Ir>) 3= --Ir The blocking input (4) (terminals 1-14) blocks the operation of one or more of the 4=1--2-- function 1U, 2U, 1f, 2f in any possible combination. Copyright 2010 - Microener...
If the error message displayed is “E2P Err”, try to program any parameter and then run “W/OTRIP”. If message disappear please check all the parameters. If message remains send the relay to Microelettrica Scientifica (or its local dealer) for repair. Copyright 2010 - Microener...
Page 25
Doc. N° MO-0068-ING IM3G-VX Rev. Pag. 25 of 36 The performances and the characteristics reported in this manual are not binding and can modified at any moment without notice Copyright 2010 - Microener...
Doc. N° MO-0068-ING IM3G-VX Rev. Pag. 28 of 36 18. CHANGE PHASE CURRENT RATED INPUT 1 OR 5A Jumper Rated input Current Phase A Rated input Current Phase B Rated input Current Phase C Copyright 2010 - Microener...
Slide-in the card on the rails provided inside the enclosure. Plug-in the card completely and by pressing the handle to the closed position. Rotate anticlockwise the screws and with the mark in the vertical position (locked). Copyright 2010 - Microener...
Page 35
Trip time delay of the second frequency element Thermal time constant of the alternator Prealarm level of the thermal image Ta/n Ta/n 0.05 Pick-up level of the active underpower element W< W< Trip time delay tW< tW< Breaker Failure function 0.05 Copyright 2010 - Microener...
Page 36
Ta/n Breaker Failure Relay reset mode A= Automatic , M = Manual tFRes: tFRes: The blocking input (2) I>> The operation of the blocking input (2) --Ir The blocking input (3) The blocking input (4) 1--2-- Copyright 2010 - Microener...