Refrigerant piping connection

When connecting refrigerant piping, do not let
substances or gases other than the specified
refrigerant enter the unit. The presence of other
gases or substances will lower the unit's capacity,
and can cause abnormally high pressure in the
refrigeration cycle. This can cause explosion and
injury.
Maximum length and drop height of refrigerant piping per unit model
Model
R410A, R32 Inverter
split air conditioner
R22 Fixed-speed split air
conditioner
R410A, R32 Fixed-speed
split Air conditioner
46 / 200 EN
Capacity (BTU/h)
< 15,000
≥15,000 and < 24,000
≥24,000 and < 36,000
< 18,000
≥18,000 and < 21,000
≥21,000 and < 35,000
< 18,000
≥18,000 and < 36,000
Note on pipe length:
The length of refrigerant piping
will affect the performance and
energy efficiency of the unit.
Nominal efficiency is tested
on units with a pipe length of
5 meters (16.5ft) (In North
C
America, the standard pipe length
is 7.5m (25')). A minimum pipe
run of 3 metres is required to
minimise vibration & excessive
noise. In special tropical area, for
the R290 refrigerant models, no
refrigerant can be added and the
maximum length of refrigerant
pipe should not exceed 10 meters
(32.8ft).
Refer to the table below for specifications on the
maximum length and drop height of piping.
Max. length (m)
25 (82ft)
30 (98.5ft)
50 (164ft)
10 (33ft)
15 (49ft)
20 (66ft)
20 (66ft)
25 (82ft)
Split type air conditioner / User Manual
Max. drop height (m)
10 (33ft)
20 (66ft)
25 (82ft)
5 (16ft)
8 (26ft)
10 (33ft)
8 (26ft)
10 (33ft)