Beko BEEPG 090 User Manual page 40

Table of Contents

Advertisement

Available languages

Available languages

8
Indoor unit installation
If refrigerant piping is already embedded in the
wall, do the following:
1. Hook the top of the indoor unit on the upper
hook of the mounting plate.
2. Use a bracket or wedge to prop up the unit,
giving you enough room to connect the
refrigerant piping, signal cable, and drain hose.
3. Connect drain hose and refrigerant piping
(refer to Refrigerant piping connection section
of this manual for instructions).
4. Keep pipe connection point exposed to perform
the leak test (refer to Electrical checks and
leak checks section of this manual).
5. After the leak test, wrap the connection point
with insulation tape.
6. Remove the bracket or wedge that is propping
up the unit.
7. Using even pressure, push down on the bottom
half of the unit. Keep pushing down until the
unit snaps onto the hooks along the bottom of
the mounting plate.
40 / 200 EN
Unit is adjustable
Keep in mind that the hooks on the mounting
plate are smaller than the holes on the back of the
unit. If you find that you don't have ample room
to connect embedded pipes to the indoor unit,
the unit can be adjusted left or right by about 30-
50mm (1.18-1.96in), depending on the model.
30-50mm
(1.18-1.96in)
Wedge
Move to left or right
Split type air conditioner / User Manual
30-50mm
(1.18-1.96in)

Advertisement

Table of Contents
loading

Table of Contents