v A new error occurs, causing the system-error LED to be lit again.

Light path diagnostics panel

The following table lists the LEDs on the light path diagnostics panel, the problems
that they indicate, and actions to solve the problems.
v Follow the suggested actions in the order in which they are listed in the Action column until the problem
is solved.
v See the parts listing in the Problem Determination and Service Guide to determine which components are
customer replaceable units (CRU) and which components are field replaceable units (FRU).
v If an action step is preceded by "(Trained service technician only)," that step must be performed only by a
trained service technician.
Lit light path
diagnostics LED with
the system-error LED
also lit
Description
All LEDs off (the
power LED is lit).
OVERSPEC
There is insufficient power to power
the system. The NON RED and
LOG LEDs might also be lit.
PS
A power supply has failed or has
been removed.
Note: In a redundant power
configuration, the dc power LED on
one power supply might be off.
LINK
There is a fault in an SMP
Expansion Port or SMP Expansion
cable.
Note: The SMP Expansion Port link
LED on the failed port is off.
Action
No action necessary.
1. Add an optional power supply if only one power
supply is installed.
2. Use 220 V ac instead of 110 V ac.
3. Reseat the following components:
a. Power supply
b. (Trained service technician only) Power
backplane
4. Remove optional devices.
5. Replace the components listed in step 3 one at a
time, in the order shown, restarting the server each
time.
1. Reinstall the removed power supply.
2. Check the individual power-supply LEDs to find the
failing power supply.
3. Reseat the following components:
a. Failing power supply
b. (Trained service technician only) Power
backplane
4. Replace the components listed in step 3 one at a
time, in the order shown, restarting the server each
time.
5. If a 12 V fault has occurred, ac power must be
removed before dc power can be restored.
1. Check the SMP Expansion Port link LEDs to find
the failing port or cable.
2. Reseat the SMP Expansion cables.
3. Replace the SMP Expansion cables.
4. (Trained service technician only) Replace the
scalability cartridge assembly. If the scalability
cartridge assembly must be replaced, call for
service.
Chapter 6. Solving problems
77