Eaton CH10GEN5030SN Instruction Booklet

Eaton CH10GEN5030SN Instruction Booklet

Corporation's family of manual transfer switches for residential and light commercial applications

Advertisement

Quick Links

Instruction Booklet IB 70-8704
Eaton Corporation's Family of Manual Transfer Switches
for Residential and Light Commercial Applications
Effective January 2009
Supplement to IB 70-8447
instruction and operation
Manual for eaton
emergency Generator
panel Model numbers:
CH10GEN5030SN
CH10GEN5030RSN
CH10GEN5050SN
CH10GEN5050RSN
Introduction
The Eaton 10 Circuit Manual Transfer Switch is
intended to be used with Eaton generators but
may be used with any generators. These Manual
Transfer Switches are rated for 50 amp utility input
and 30 amp or 50 amp generator input respec-
tively at 240 Vac. These devices come equipped
to power nine emergency circuits. There are eight
single-pole emergency circuit breakers and one
2- pole emergency circuit breaker included.
These devices are intended for use with genera-
tors that are wired as either Separately Derived
systems (neutral and ground bonded together
at the generator – typically protected by a GFCI,
ground fault circuit interrupter, on the generator)
or Non-Separately Derived systems (neutral and
ground are NOT bonded at the generator). Refer
to the NFPA 70, National Electrical Code, for
proper connection and further definition.
Contact the generator manufacturer if you
are unsure how the generator is configured
(Separately Derived or Non-Separately Derived). It
is extremely important that you know this informa-
tion prior to connecting the generator to this or
any other transfer switch.
CH10GEN5030SN
CH10GEN5030RSN
CH10GEN5050SN
CH10GEN5050RSN

Advertisement

loading

Summary of Contents for Eaton CH10GEN5030SN

  • Page 1 • CH10GEN5050RSN • Introduction The Eaton 10 Circuit Manual Transfer Switch is intended to be used with Eaton generators but may be used with any generators. These Manual Transfer Switches are rated for 50 amp utility input and 30 amp or 50 amp generator input respec- tively at 240 Vac.
  • Page 2 Instruction Booklet IB 70-8704 Eaton Corporation’s Family of Manual Transfer Switches for Residential and Light Commercial Applications Effective January 2009 Slide Interlock (To operate, turn the utility breaker to the OFF position. Lift the interlock and hold. Utility Breaker Shown...
  • Page 3 Eaton Corporation’s Family of Manual Transfer Switches Instruction Booklet IB 70-8704 for Residential and Light Commercial Applications Effective January 2009 Utility Neutral Utility Pole #1 Utility Pole #2 Do Not Connect the Utility or Generator Neutrals to the Generator Neutral...
  • Page 4 The information, recommendations, descriptions, and safety nota- tions in this document are based on Eaton’s experience and judg- ment with respect to Retrofitting of Power Breakers. This instruction- al literature is published solely for information purposes and should not be considered all-inclusive.

This manual is also suitable for:

Ch10gen5030rsnCh10gen5050snCh10gen5050rsn