Allow as much room as possible when using elbows or making
turns. Bend vent gradually to avoid kinking.
Vent outlet is located at the back of the dryer, at bottom center.
The vent can be routed up, down, left, right, behind the dryer,
or straight out the back of the dryer. See "Product Dimensions"
in the "Location Requirements" section.
Make-up air:
Although each single-load dryer should have an unobstructed
outdoor air opening of 24 in
per 1,000 B.T.U. [252 kcal]), common make-up air openings are
also acceptable. Set up common openings so that the make-up
air is distributed equally to all of the dryers. Keep in mind that
the coverage area must be increased by 33% to account for
use of registers or louvers over the openings. Also, make-up air
openings should not be installed near the location
of exhaust vents exiting the building.
Vent System Length
Maximum length of vent system depends upon the type of
vent used, number of elbows, and type of exhaust hood.
The maximum length for rigid vent is shown in the chart.
Maximum Vent Length
4" (102 mm) Diameter Exhaust Hoods
Box
Vent System Chart (Rigid Metal Vent)
No. of 90°
Box Hood and
Turns
Louvered Style
0
130 ft (39.6 m)
1
125 ft (38.1 m)
2
115 ft (35.1 m)
3
106 ft (32.3 m)
4
98 ft (29.9 m)
For vent systems not covered by the vent specification chart,
see your parts distributor.
Provision must be made for enough air for combustion and
ventilation. (Check governing codes and ordinances.) See
"Recessed Area and Closet Installation Instructions" in the
"Location Requirements" sections.
A 4" (102 mm) outlet hood is preferred. However, a 2
outlet exhaust hood may be used. A 2
greater back pressure than other hood types. For permanent
installation, a stationary vent system is required.
Connect Vent
1. If connecting to existing vent, make sure the vent is clean.
2. Using a 4" (102 mm) clamp, connect vent to exhaust outlet
in dryer.
NOTE: Do not remove vent collar.
(154 cm
) (based on 1 in
2
2
2
2
" (63.5 mm) Angled
Louvered
1
2
Angled Hood Style
129 ft (39.3 m)
119 ft (36.3 m)
109 ft (33.2 m)
100 ft (30.5 m)
92 ft (28.0 m)
1
2
/
" (64 mm) outlet creates
1
2
Vent Collar
3. Tighten hose clamp with Phillips screwdriver.
[6.5 cm
]
2
4. Make sure the vent is secured to exhaust hood with
a 4" (102 mm) clamp.
5. Move dryer into final position. Do not crush or kink vent.
Make sure dryer is level.
NOTE: Testing for proper ventilation should be done with a
Manometer. Minimum: 0.01" (0.2 mm). Maximum: 0.6" (16 mm).
For vent systems not covered by the vent specification chart,
see your parts distributor.
If dryer is installed in a confined area, such as a bedroom,
bathroom, or closet, provision must be made for enough air
for combustion and ventilation. (Check governing codes and
ordinances.) See "Recessed Area and Closet Installation
Instructions" in the "Location Requirements" section.
A 4" (102 mm) outlet hood is preferred. However, a 2
outlet exhaust hood may be used. A 2
greater back pressure than other hood types. For permanent
installation, a stationary vent system is required.
If An Exhaust Hood Cannot Be Used
The outside end of the main vent should have a sweep elbow
directed downward.
" (64 mm)
If the main vent travels
vertically through the roof,
rather than through the wall,
install a 180° sweep elbow
on the end of the vent at
least 2 ft (610 mm) above the
highest part of the building.
The opening in the wall or
roof shall have a diameter
1/2" (13 mm) larger than
the vent diameter. The vent
should be centered in the
opening.
Do not install screening or
cap over the end of the vent.
" (64 mm)
1
2
" (64 mm) outlet creates
1
2
* Minimum
clearance above
any accumulation
12" minimum
(305 mm)*
of snow, ice,
or debris such
as leaves
24" minimum
(610 mm)