Installation Preparation

TYPE OF ELECTRIC CONNECTIONS
A power supply kit must be used to supply power to the
Models must be installed using the appropriate GE
Appliances power supply kit for the branch circuit
amperage and the electrical resistance heater wattage
select the appropriate kit.
connection of components is done in accordance with
electrical codes.
External Disconnect
supply located within line of sight of the closet door
means shall be readily accessible while the air
shall not obscure the rating plate or be located on
the access panel or closet door. A properly rated field
supplied switch is a common means for electrical
disconnection.
POWER CONNECTION CHART
Power Supply Kits
230 / 208 Volt
Range: 187v - 254v
Power Supply Kits
265 Volt*
Range: 249v - 293v
49-5000640 Rev. 2
Direct Connections
Configuration
Heater Wattage
Direct Connection
@ 230 / 208 Volt
Hard Wired
Hard Wired
Hard Wired
Configuration
Heater Wattage
Direct Connection
Hard Wired
Hard Wired
Hard Wired
Power Supply Kit Direct Connect
208/230/265 Volt Applications
MPORTANT: Connection to a branch circuit MUST
be done by direct connection in accordance with the
building mounted exposed receptacle is not permitted
by code.
@ 265 Volt
Circuit Protective Device
Circuit Protective Device