Installation - Bosch ODU-FA Installation & User Manual

Outdoor unit failure alarm

Advertisement

3.

INSTALLATION

Instruction:
1. Below is an example of how to install, when connecting to a computer;
2. The maximum of one fault alarm can connect to a computer;
3. One computer can connect to a fault alarm or a centralised controller, but not both together;
4. One computer can connect to the maximum of 32 outdoor units;
5. When this fault alarm module is connected to a computer with a third network control system, the default address for the alarm module will be 16
and this cannot be changed.
6. Electrical power supply and fault output.
Fault alarm output module
Fault alarm cover
Fault alarmoperation,
fault display lamp
CLIMATE 5000 VRF
Power input AC
198-242 V
Self-furnish power
strips2*0.75mm²
Fault alarm base
Fault alarm main control panel
Fault alarm output AC
Self-furnish wire2*0.75mm²
Electrical appliance current
used for fault alarm < 3.15A
Fix the base at the holes,
and use the cross screwdriver
to screw the cross recessed pan
head tapping screws into the
plastic expanded tube,and fix the base.
Use electric drill to drill four holes with φ6mm
and depth are 30mm, and then put the plastic
expanded tube into the holes.
INSTALLATION | 3
198-242 V
6 720 862 462 (2017/05)