Text message
Out of specification
Text message
S600
Impermissible
electronics
temperature
S601
Overfilling
S603
Impermissible
operating voltage
Maintenance
Text message
M500
Error in the
delivery status
M501
Error in the
non-active
linearization
table
M507
Error in the
transmitter
settings
M508
No executable
Bluetooth
software
M509
Software update
running
M510
No
communication
SITRANS LR110, HART
Operating Instructions, 10/2023, A5E49829006
Code
Code
Temperature of the electronics
in the non-specified range
Danger of vessel overfilling
Terminal voltage too small
Code
The data could not be restored
during the reset to delivery
status
Hardware error EEPROM
Error during setup
Error when carrying out a
reset
Auto false echo suppression
faulty
Checksum error in Bluetooth
software
Software update running
Communication between main
electronics and display module
disturbed
10.4 Status messages according to NE 107
Cause
Wait for the automatic end
after 60 mins.
Cause
Check ambient temperature
Insulate electronics
Make sure that there is no
further filling
Check level in the vessel
Check terminal voltage,
increase operating voltage
Cause
Repeat reset
Load XML file with transmitter
data into the transmitter
Send transmitter for repair
Carry out reset and repeat
setup
Carry out software update
Wait until software update is
finished
Check the connection cable to
the display
Send transmitter for repair
Diagnostics and troubleshooting
Rectification
State in CMD 48
"Standardized
Status 0"
Rectification
State in CMD 48
Byte 23, Bit 4 of
Byte 14 ... 24
Byte 23, Bit 5 of
Byte 14 ... 24
Byte 23, Bit 6 of
Byte 14 ... 24
Rectification
State in CMD 48
Bit 0 of
Byte 14 ... 24
Bit 1 of
Byte 14 ... 24
Bit 7 of
Byte 14 ... 24
Bit 8 of
Byte 14 ... 24
Bit 9 of
Byte 14 ... 24
Bit 10 of
Byte 14 ... 24
DevSpec
DevSpec
DevSpec
41