Device configuration

Components

Select
PV generator
Activate the particular PV generator and enter the connected PV power in the
associated field.
Primary meter
To ensure smooth operation in conjunction with other energy producers, it is im-
portant to install the Fronius Smart Meter at the feed-in point. The inverter and
other producers must be connected to the public grid via the Fronius Smart
Meter.
This setting also affects how the inverter behaves overnight. If the function is de-
activated, the inverter switches to standby mode as soon as there is no more PV
power available. The message "Power low" is displayed. The inverter starts again
as soon as sufficient PV power is available.
After connecting the meter, the position must be configured.
Several Fronius Smart Meters can be installed in the system. A different address
needs to be set for each Smart Meter.
The Watt value on the generator meter is the sum of all generator meters. The
Watt value on the consumption meter is the value of all consumption meters.
Ohmpilot
All Ohmpilots available in the system are displayed. Select the desired Ohmpilot
and add it to the system via "Add".
Functions and
Load management
IOs
Up to four pins can be selected here for load management. Other load manage-
ment settings are available in the Load Management menu item.
Default: Pin 1
OFF - Demand Response Mode (DRM)
The pins for control via DRM can be set here:
Mode
DRM0
76
"Add component+"
to add all available components to the system.
Description
Inverter disconnects itself
from the grid
REF GEN
COM LOAD
Information
Open grid relay
DRM0 occurs if there is an in-
terruption or short circuit on
the REF GEN or COM LOAD
leads. Or if the combinations
DRM1 - DRM8 are invalid.
De-
fault
pin
RG0
CL0