VENTILATION FOR BUILT-IN INSTALLATIONS

1. At least one ventilation opening shall be provided on the exposed exterior side of the enclosure located within 5
inches (127 mm) of the top of the enclosure and unobstructed. The opening(s) shall have a total free area of not
less than 1 in
/lb (14.2 cm
2
2. At least one ventilation opening shall be provided on the exposed, exterior side of the enclosure 1 inch (25.4 mm)
or less from the floor level and shall have a total free area of not less than 1/2 in
capacity. The upper edge shall be no more than 5 inches (127 mm) above the floor level.
3. Every opening shall have a minimum dimension so as to permit the entrance of a 1/8 inch (3.2 mm) rod.
Vents
5.00 inch
maximum
No more than 5.00 inches above
the floor of the installation.
/kg) of stored fuel capacity.
2
10
Not less than
5.00 inches
from inside
bottom of
countertop.
5.00 inch
maximum
1.00 inch maximum
Not less than
1.00 inch from
inside floor of
installation.
2
/lb (7.1 cm
2
/kg) of stored fuel