Alarm List - Daikin Maverick I Installation And Maintenance Manual

Commercial packaged rooftop systems
Hide thumbs Also See for Maverick I:
Table of Contents

Advertisement

Alarm List

Table 13: Alarm and Diagnostic List
Alarm Designation
No Active Alarm
Locked Rotor Circuit 1
Open Circuit 1
Missing Phase Circuit 1
Reverse Phase Circuit 1
Welded Contactor
Circuit 1
Low Voltage Circuit 1
Low Voltage
Controller
Failed Ignition
Low Flame Sense
Flame Lost
Unexpected Flame
AC Low Pressure Switch
1 Trip-LP1
Controller
AC Low Pressure Switch
2 Trip-LP2
Controller
McQuay OM 1077
Origin
Comfort Alert Code 4.
CA1
Circuit 1 shutdown and retry after Anti-Short Cycle
Delay (ASCD). Maximum is 3 attempts.
Comfort Alert Code 5.
Circuit 1 shutdown and retry after ASCD.
CA1
Note: This alarm is sent by the Comfort Alert Module
only after the fault has been sensed for a minimum
of 4 hours.
Comfort Alert Code 6
CA1
Circuit 1 shutdown
Comfort Alert Code 7
CA1
Circuit 1 shutdown.
Comfort Alert Code 8
Run outdoor and indoor fans continuously for circuit
CA1
2 and change mode of operation to Unoccupied
Auto. This procedure prevents the Space
Temperature from reaching extreme values.
Comfort Alert Code 9. Shutdown and wait for voltage
CA1
to return to operational levels.
DDC
De-energize all relay outputs.
IFC
IFC locks out for 1 hour
IFC flashes error code on LED, transmits the
IFC
warning through the network, but otherwise
operates normally
If lost 17 times within single call for heat, locks out
IFC
for 1 hour. Otherwise retry ignition.
IFC Energizes inducer and main blower. Locks out
IFC
for 1 hour
If the low pressure switch trips 3 times within 120
minutes of operation during the same call for heating
DDC
operation, the control will lock out compressor and
outdoor fan operation. If the lock-out due to low
pressure occurs at an outdoor ambient temperature
below 5 °F, the control will automatically exit the
DDC
lock-out mode when the outdoor ambient
temperature rises above 5 °F. LPS is ignored during
defrost.
Description
Alarm List
Status/Troubleshooting Information
• Low line voltage
• Excessive Refrigerant in compressor
• Seized bearings in compressor
• Condensing unit power disconnect is open
• Compressor circuit breaker or fuses are open
• Compressor contactor has failed open
• High pressure switch is open and requires
manual reset
• Broken supply wires or connector is not making
contact
• Unusually long compressor protector reset time
due to extreme ambient temperature
• Compressor windings are damaged
• Compressor fuse is open on one phase
• Broken wire or connector on one phase
• Compressor motor winding is damaged
• Utility supply has dropped one phase
• Compressor running backward due to supply
phase reversal
• Compressor contactor has failed closed
• Thermostat demand signal not connected to
module
• Control circuit transformer is overloaded
• Low line voltage to compressor
• Gas Valve Not Turned On
• Little or No Supply Gas
• Incorrect Manifold Pressure
• No Ignition Source, Direct Spark Ignition (DSI)
• No 24 Volt Power to Gas Valve
• Bad Gas Valve
• Dirty Flame Sensor
• Unit Not Properly Grounded
• Incorrect Polarity
• Flame Sensor Incorrectly Wired
• Bad Flame Sensor
• Unit has low refrigerant charge
• Indoor coil frozen (cooling mode)
• Dirty indoor coil or filter (cooling mode)
• Outdoor coil is frozen (heating mode)
• Expansion valve in not operating correctly
23