Unit Installation
• Y2 - Second Stage of compressor
• B - Not Used
• W1 - First Stage Auxiliary heat (electric or gas)
• W2 - Second Stage Auxiliary heat (electric or gas)
• L - Comfort Alert signal (output)
• R & C - 24VAC
Figure 3: Thermostat Inputs and Outputs
+24VAC
1st Stage
Compressor
2nd Stage
Compressor
Indoor Fan
24V Common
Figure 4: Standalone with Zone Sensor and Time Clock
Zone Sensor
10k Thermistor
Override
Button
5k
10k Pot
Setpoint Adj.
10
Comfort
Alert
Not Used
Occupancy
Signal
2nd Stage Heat
1st Stage Heat
2k
Standalone with Zone Sensor and Time Clock
If Occupied Mode is set to any of the options other than "Off"
and "Control By Thermostat", the control will operate in Stand
Alone mode or network using its local temperature sensors to
determine demand. The system can be set up with a zone
sensor to determine heat or cool demand and a solid state time
clock to determine occupancy. (See
17)
Time Clock
Occupied Mode‚ page