Daikin ETBH16E9W Installer's Reference Manual page 267

Table of Contents

Advertisement

EPRA14~18D + ETBH/X16E
Daikin Altherma 3 H HT W
4P644736-1D – 2023.10
#
Action
5
Return to the default situation.
Press BS1 once.
(a)
= OFF,
= ON, and
Result: The recovery mode is activated. The unit opens the electronic expansion
valves.
To deactivate the recovery mode
After recovering refrigerant, deactivate the recovery mode as follows:
#
Procedure
1
Start from the default situation.
2
Select mode 2.
Press and hold BS1 for 5 seconds.
3
Select setting 9.
Press BS2 9 times.
4
Select value 1.
a
Display the current value.
Press BS3 once.
b
Change the value to 1.
Press BS2 once.
c
Enter the value in the system.
Press BS3 once.
d
Confirm.
Press BS3 once.
5
Return to the default situation.
Press BS1 once.
(a)
= OFF,
= ON, and
Result: The recovery mode is deactivated. The unit returns the electronic
expansion valves to their initial state.
INFORMATION
Power OFF. When power is turned OFF and turned ON again, the recovery mode is
deactivated automatically.
= flashing.
= flashing.
15
Disposal
|
(a)
7-segments display
(a)
7-segments display
Installer reference guide
267