Preparing the installation site............................57 6.1.1 Installation site requirements of the outdoor unit..................57 6.1.2 Additional installation site requirements of the outdoor unit in cold climates..........59 Installer reference guide EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 3
Possible screens ................................120 9.3.1 Possible screens: Overview ..........................120 9.3.2 Home screen..............................121 9.3.3 Main menu screen............................124 9.3.4 Menu screen..............................125 9.3.5 Setpoint screen............................... 125 EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 4
To display the help text in case of a malfunction ..................225 13.4.2 Error codes: Overview ............................ 226 14 Disposal 14.1 To recover refrigerant..............................231 15 Technical data Installer reference guide EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 5
Piping diagram: Indoor unit ............................237 15.4 Wiring diagram: Outdoor unit ............................238 15.5 Wiring diagram: Indoor unit ............................243 16 Glossary 17 Field settings table EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Indicates a situation that could result in death or serious injury. WARNING: FLAMMABLE MATERIAL CAUTION Indicates a situation that could result in minor or moderate injury. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Improper installation or attachment of equipment or accessories could result in electric shock, short-circuit, leaks, fire or other damage to the equipment. Only use accessories, optional equipment and spare parts made or approved by Daikin. WARNING Make sure installation, testing and applied materials comply with applicable legislation (on top of the instructions described in the Daikin documentation).
If applicable. See the installation manual or installer reference guide of your application for more information. NOTICE Make sure refrigerant piping installation complies with applicable legislation. In Europe, EN378 is the applicable standard. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 9
▪ The unit is factory charged with refrigerant and depending on pipe sizes and pipe lengths some systems require additional charging of refrigerant. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
1.2.5 Water If applicable. See the installation manual or installer reference guide of your application for more information. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 12
Running the product in reversed phase can break the compressor and other parts. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Latest revisions of the supplied documentation may be available on the regional Daikin website or via your dealer. The original documentation is written in English. All other languages are translations. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
About the documentation Technical engineering data ▪ A subset of the latest technical data is available on the regional Daikin website (publicly accessible). ▪ The full set of latest technical data is available on the Daikin Business Portal (authentication required).
Page 15
Note: There is also an installer settings table in the user reference guide. This table has to be filled in by the installer and handed over to the user. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
To avoid injury, do NOT touch the air inlet or aluminium fins of the unit. Crane Keep the slings within the marked area to not damage the unit. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 17
After unpacking, carry the unit using the slings attached to the unit. See also: ▪ "3.2.2 To unpack the outdoor unit" [ 18] ▪ "6.3.4 To install the outdoor unit" [ 67] ±150 4× EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
About the box 3.2.2 To unpack the outdoor unit a, b Accessories EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Installation manual – Discharge grille NOTICE Unpacking – Front corners. When you remove the front packaging corners, hold the box containing the discharge grille to prevent it from falling. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Addendum book for optional equipment c Indoor unit installation manual d Operation manual e Sealing ring for shut-off valve f Shut-off valve g Overpressure bypass valve h Wall bracket EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Location Model identification Example: EP R A 14 DA V3 Code Explanation European hydro-split outdoor pair heat pump High water temperature – ambient zone 2 (see operation range) Refrigerant R32 EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
When using a third-party tank, make sure it complies with the minimum requirements (see "Third-party tank requirements" [ 22]). Third-party tank requirements In case of a third-party tank, the tank shall adhere to the following requirements: EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
For installation instructions, see the installation manual of the control, and the addendum book for optional equipment. Wireless room thermostat (EKRTR1) You can connect an optional wireless room thermostat to the indoor unit. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 24
For installation instructions, see the installation manual of the remote outdoor sensor and the addendum book for optional equipment. INFORMATION You can only connect either the remote indoor sensor or the remote outdoor sensor. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 25
Use the connection kit to convert a heating only model to a reversible model. For installation instructions, see the installation manual of the conversion kit. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 26
For installation instructions, see the installation and operation manual of the Human Comfort Interface (HCI) as room thermostat. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Setting up the domestic hot water tank ▪ Setting up the energy metering ▪ Setting up the power consumption control ▪ Setting up an external temperature sensor EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
▪ For more information about connecting the electrical wiring to the unit, see: "8.2 Connections to the outdoor unit" [ 92] "8.3 Connections to the indoor unit" [ 99] EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 29
▪ For more information about connecting the electrical wiring to the unit, see: "8.2 Connections to the outdoor unit" [ 92] "8.3 Connections to the indoor unit" [ 99] EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 30
Code: [C-05] heating or cooling demand. Benefits ▪ Wireless. The Daikin external room thermostat is available in a wireless version. ▪ Efficiency. Although the external room thermostat only sends ON/OFF signals, it is specifically designed for the heat pump system. ▪...
Page 31
The underfloor heating The heat pump convectors ▪ Space cooling is provided by the heat pump convectors only. The underfloor heating is shut off by the shut-off valve. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 32
Unit operation is decided by the ▪ #: [2.9] external thermostat. ▪ Code: [C-07] Number of water temperature zones: 0 (Single zone): Main ▪ #: [4.4] ▪ Code: [7-02] EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
▪ For more information about connecting the electrical wiring to the unit, see: "8.2 Connections to the outdoor unit" [ 92] "8.3 Connections to the indoor unit" [ 99] EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 34
99] ▪ For each room, a shut-off valve (field supplied) is installed to avoid leaving water supply when there is no heating or cooling demand. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 35
▪ For more information about connecting the electrical wiring to the unit, see: "8.2 Connections to the outdoor unit" [ 92] "8.3 Connections to the indoor unit" [ 99] EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 36
Combination: Underfloor heating + Heat pump convectors – Multiple rooms Setup A Main leaving water temperature zone B Room 1 C Room 2 a External room thermostat EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Main zone = Zone with the lowest design temperature in heating, and the highest design temperature in cooling ▪ Additional zone = Zone with the highest design temperature in heating, and the lowest design temperature in cooling EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 38
▪ For more information about connecting the electrical wiring to the unit, see: "8.2 Connections to the outdoor unit" [ 92] "8.3 Connections to the indoor unit" [ 99] EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 39
OFF condition. No separation between ▪ #: [3.A] heating or cooling demand. ▪ Code: [C-06] Shut-off valve output Set to follow the thermo demand of the main zone. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
During heating operation of the auxiliary boiler, the auxiliary boiler operates to achieve the desired water temperature set via the auxiliary boiler controller. Setup ▪ Integrate the auxiliary boiler as follows: EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 41
Make sure the auxiliary boiler and its integration in the system complies with applicable legislation. ▪ Daikin is NOT responsible for incorrect or unsafe situations in the auxiliary boiler system. ▪ Make sure the return water to the heat pump does NOT exceed 60°C. To do so: Set the desired water temperature via the auxiliary boiler controller to maximum 60°C.
Page 42
To prevent freeze-up of the water piping, the auxiliary gas boiler must have a fixed setpoint ≥55°C, or a weather-dependent setpoint ≥T (°C) –30 –25 –20 –15 –10 –5 (°C) Outdoor temperature Minimum weather-dependent setpoint for auxiliary gas boiler EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Are there any other domestic hot water — needs? Example: If the DHW consumption of a family (4 persons) per day is as follows: ▪ 3 showers ▪ 1 bath EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 44
DHW tank during the day. If energy prices are lower during the night, we recommend to heat up the DHW tank during the night. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
The DHW pump and the installation are field supply and the responsibility of the installer. For the electrical wiring, see "8.3.5 To connect the domestic hot water pump" [ 109]. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
DHW pump and heater element (if needed) as shown above. Configuration The indoor unit can control DHW pump operation. For more information, see "9 Configuration" [ 116]. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
You can read out the energy data: For space heating For space cooling For domestic hot water production ▪ You can read out the energy data: Per month Per year EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Setup and configuration: To get accurate energy data, measure the capacity (resistance measurement) and set the capacity via the user interface for: The backup heater (step 1 and step 2) (if applicable) The booster heater EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Backup heater supplied from a three- (*6V (6T1): 3~ 230 V) phase grid (i.e. the backup heater (*9W: 3N~ 400 V) model is *9W or *6V connected to a three-phase grid) EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
5.5.4 Preferential kWh rate power supply General rule ▪ Power meter 1: Measures the outdoor unit. ▪ Power meter 2: Measures the rest (i.e. indoor unit, backup heater and optional booster heater). EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Allows you to limit the power consumption of the entire heat pump system (sum of indoor unit and backup heater) with one permanent setting. ▪ Limitation of power in kW or current in A. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
"Power consumption control" [ 187]): Select continuous limitation mode Select the type of limitation (power in kW or current in A) Set the desired power limitation level EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
5.6.2 Power limitation activated by digital inputs Power limitation is also useful in combination with an energy management system. The power or current of the entire Daikin system is limited dynamically by digital inputs (maximum four steps). Each power limitation level is set via the user interface by limiting one of the following: ▪...
Consumed energy A Outdoor unit B Booster heater C Backup heater a Limited outdoor unit operation b Full outdoor unit operation c Booster heater turned ON EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
You can connect one external temperature sensor. It measures the indoor or outdoor ambient temperature. We recommend to use an external temperature sensor in the following cases: EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 56
To protect the outdoor unit, the internal sensor of the outdoor unit is always used. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Do NOT hang the unit on a ceiling. Strong winds (≥18 km/h) blowing against the outdoor unit’s air outlet causes short circuit (suction of discharge air). This may result in: EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 58
This is to prevent corrosion caused by high levels of salt in the air, which might shorten the life of the unit. Install the outdoor unit away from direct sea winds. Example: Behind the building. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
WARNING Make sure installation, servicing, maintenance and repair comply with instructions from Daikin and with applicable legislation (for example national gas regulation) and are executed only by authorised persons. 6.1.2 Additional installation site requirements of the outdoor unit in cold climates Protect the outdoor unit against direct snowfall and take care that the outdoor unit is NEVER snowed up.
Maximum height difference between domestic hot water tank 10 m and outdoor unit Maximum water piping length between indoor unit and 10 m domestic hot water tank EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Calculation tool. The Hydronic Piping Calculation tool is part of the Heating Solutions Navigator which can be reached via https:// professional.standbyme.daikin.eu. Please contact your dealer if you have no access to Heating Solutions Navigator. ▪ Mind the following spacing installation guidelines: ≥500...
3 Remove the transportation stays (2×), and dispose of them. 6.2.4 To close the outdoor unit NOTICE When closing the outdoor unit cover, make sure that the tightening torque does NOT exceed 4.1 N•m. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
3 Switch box 4 User interface panel Open 1 Remove the front panel. 2 If you have to connect electrical wiring, remove the switch box cover. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 64
5 Optional: Remove the user interface panel. NOTICE If you remove the user interface panel, also disconnect the cables from the back of the user interface panel to prevent damage. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
6.3.2 Precautions when mounting the outdoor unit INFORMATION Also read the precautions and requirements in the following chapters: ▪ "1 General safety precautions" [ 6] ▪ "6.1 Preparing the installation site" [ 57] EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
When installing on a pedestal, make sure that the discharge grille still can be put in its safety position. See "6.3.7 To remove the discharge grille, and put the grille in safety position" [ 70]. 4× M12 (mm) EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
1 Carry the unit by its slings, and put it onto the installation structure. ±150 4× 2 Fix the unit to the installation structure. 4× M12 3 Remove the slings (and screws), and dispose of them. 4× EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Provide at least 150 mm of free space below the unit. Additionally, make sure the unit is positioned at least 100 mm above the expected level of snow. Use the drain plug (with O-ring) and a hose for drainage. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
4 Align and attach the left side. 5 Align and attach the middle part. 6 Align and attach the right side. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
69] ▪ "6.3.7 To remove the discharge grille, and put the grille in safety position" [ 70] 1 Remove the upper part of the discharge grille. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 71
4 Align the ball stud and hook on the grille with their counterparts on the unit. 5 Insert the hook. 6 Insert the ball stud. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Optional: If you want to fix the unit to the wall from inside the unit, provide an additional screw plug. 2 Lift the unit. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 73
▪ Remove the upper front panel, and open the switch box. See "6.2.5 To open the indoor unit" [ 63]. ▪ Fix the unit to the wall with an Ø8 mm screw. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
1 Connect a drain tube (field supply) to the drain pan connector as follows: a Drain pan connector It is recommended to use a tundish to collect the water. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Closed circuit. Use the indoor unit ONLY in a closed water system. Using the system in an open water system will lead to excessive corrosion. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 76
Drainage – Pressure relief valve. Connect the drain hose properly to the drain to avoid water dripping out of the unit. See "6.4.4 To connect the drain hose to the drain" [ 74]. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Recirculation pump 7.1.2 Formula to calculate the expansion vessel pre-pressure The pre-pressure (Pg) of the vessel depends on the installation height difference (H): Pg=0.3+(H/10) (bar) EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
"7.2.5 To protect the water circuit against freezing" [ 83]. Use the following graph to determine the maximum water volume for the calculated pre-pressure. 200 220 A Pre-pressure (bar) EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 79
NOT be displayed on the user interface. In this case, the minimum flow rate can be checked by way of the pump test (check that the user interface does NOT display error 7H). EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Example 2 The indoor unit is installed at the highest point in the water circuit. The total water volume in the water circuit is 250 l. Actions: EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Deformation of the piping can cause malfunctioning of the unit. Outdoor unit 1 Connect the shut-off valve (with integrated filter) to the outdoor unit water inlet, using thread sealant. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 82
3 Connect the space heating/cooling field piping on the space heating water OUT connection (b) of the indoor unit. a Water IN (screw connection, 1") b Space heating water OUT (screw connection, 1") EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Do one of the following to protect the water circuit against freezing: ▪ Add glycol to the water. Glycol lowers the freezing point of the water. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 84
To prevent the system from freezing, more glycol is required. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 85
To install freeze protection valves To protect the field piping against freezing, install the following parts: EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
7.2.7 To insulate the water piping The piping in the complete water circuit MUST be insulated to prevent condensation during cooling operation and reduction of the heating and cooling capacity. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 87
Please contact your dealer if you have no access to Heating Solutions Navigator. This recommendation ensures good operation of the unit, however, local regulations may differ and shall be followed. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
▪ Make electrical connections to the fixed wiring. ▪ All components procured on-site and all electrical construction MUST comply with the applicable legislation. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Place the round crimp-style terminal on the wire up to the covered part and fasten the terminal with the appropriate tool. Stranded conductor wire Round crimp-style terminal ▪ Use the following methods for installing wires: EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
5 Normal kWh rate power supply (to power the indoor unit PCB in the event of power supply interruption of the preferential kWh rate power supply) EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
4 Inside the switch box, connect the wires to the appropriate terminals, and fix the cables with cable ties. See: ▪ "In case of V3 models" [ 93] ▪ "In case of W1 models" [ 95] EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 93
▪ Connect the wires to the terminal block (make sure the numbers match with the numbers on the indoor unit) and the earth screw. ▪ Fix the cable with a cable tie. Wires: (3+GND)×1.5 mm² — EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 94
▪ Fix the cable with cable ties. Wires: (2+GND)×0.75 mm². Wiring must be double insulated. Maximum power allowed for drain tube heater = 115 W (0.5 A) — EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 95
▪ Connect the wires to the terminal block. ▪ Fix the cable with a cable tie. Use the factory-mounted cable. Wires: 3N+GND Maximum running current: Refer to name plate on unit. — EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 96
▪ Connect the wires to the terminal block (make sure the numbers match with the numbers on the indoor unit) and the earth screw. ▪ Fix the cable with a cable tie. Wires: (3+GND)×1.5 mm² — EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 97
▪ Fix the cable with cable ties. Wires: (2+GND)×0.75 mm². Wiring must be double insulated. Maximum power allowed for drain tube heater = 115 W (0.5 A) — EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
8.2.2 To reposition the air thermistor on the outdoor unit This procedure is only necessary in areas with low ambient temperatures. Required accessory (delivered with the unit): Thermistor fixture. Click EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Maximum running current: 100 mA For the main zone: ▪ [2.9] Control ▪ [2.A] Thermostat type For the additional zone: ▪ [3.A] Thermostat type ▪ [3.9] (read-only) Control EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 100
▪ Installation manual of the remote indoor sensor ▪ Addendum book for optional equipment Wires: 2×0.75 mm² [9.B.1]=2 (External sensor = Room) [1.7] Room sensor offset EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 101
Installation manual of the domestic hot heater (to indoor unit) water tank ▪ Addendum book for optional equipment Wires: 2+GND Maximum running current: 13 A [9.4] Booster heater EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Maximum length: 200 m See below ("LAN adapter – System requirements"). LAN adapter – System requirements The requirements posed on the Daikin Altherma system depend on the LAN adapter application/system layout (app control, or Smart Grid application). App control: Item Requirement...
Page 103
Maximum length: 50 m. Preferential kWh rate power supply contact: 16 V DC detection (voltage supplied by PCB). The voltage-free contact shall ensure the minimum applicable load of 15 V DC, 10 mA. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 104
The preferential kWh rate power supply contact is connected to the same terminals (X5M/9+10) as the safety thermostat. Thus, the system can have EITHER preferential kWh rate power supply OR a safety thermostat. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Electrical equipment complying with EN/IEC 61000-3-12 (European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16 A and ≤75 A per phase). EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 106
Field wiring (see table below) Model (power supply) Connections to backup heater power supply *6V (6V: 1N~ 230 V) Q1DI 1N~, 50 Hz 230 V AC EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
For more information, see the installer reference guide. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
3 Fix the cable with cable ties to the cable tie mountings. 8.3.4 To connect the electricity meters Wires: 2 (per meter)×0.75 mm² Electricity meters: 12 V DC pulse detection (voltage supplied by PCB) EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
8.3.5 To connect the domestic hot water pump Wires: (2+GND)×0.75 mm² DHW pump output. Maximum load: 2 A (inrush), 230 V AC, 1 A (continuous) [9.2.2] DHW pump [9.2.3] DHW pump schedule EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
1 Front panel 2 Switch box cover 3 Switch box 2 Connect the alarm output cable to the appropriate terminals as shown in the illustration below. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Heating only models + conversion kit (EKHBCONV) Wires: (2+1)×0.75 mm² Maximum load: 0.3 A, 250 V AC — 1 Open the following (see "6.2.5 To open the indoor unit" [ 63]): EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
8.3.8 To connect the changeover to external heat source Wires: 2×0.75 mm² Maximum load: 0.3 A, 250 V AC Minimum load: 20 mA, 5 V DC [9.C] Bivalent 1 Open the following (see "6.2.5 To open the indoor unit" [ 63]): EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
2 Switch box cover 3 Switch box 2 Connect the power consumption digital inputs cable to the appropriate terminals as shown in the illustration below. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
2 Switch box cover 3 Switch box 2 Connect the safety thermostat (normally closed) cable to the appropriate terminals as shown in the illustration below. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 115
The preferential kWh rate power supply contact is connected to the same terminals (X5M/9+10) as the safety thermostat. Thus, the system can have EITHER preferential kWh rate power supply OR a safety thermostat. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
First time – Configuration wizard. When you turn ON the user interface for the first time (via the indoor unit), the configuration wizard starts to help you configure the system. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Confirm the pin code and proceed. Installer pin code The Installer pin code is 5678. Additional menu items and installer settings are now available. Installer 5678 EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 118
4 Turn the left dial to select the second part of the setting 01 15 5 Turn the right dial to modify the value from 15 to 20. 01 20 EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Comfort setpoint [5.2] Eco setpoint [5.3] Reheat setpoint [5.4] Hysteresis [5.9] and [5.A] 9.3 Possible screens 9.3.1 Possible screens: Overview The most common screens are as follows: EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
26 Feb 2019 22:19 Possible actions on this screen Go through the list of the main menu. Go to the main menu screen. Enable/disable breadcrumbs. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 122
Outdoor unit Indoor unit / domestic hot water tank Floor-standing indoor unit with integrated tank Wall-mounted indoor unit Wall-mounted indoor unit with separated tank Water pressure EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 123
"13.4.1 To display the help text in case of a malfunction" [ 225] for more information. If the corresponding operation (for example: space heating) is not active, the circle is greyed out. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Displays data and information about the Information indoor unit. Installer settings Restriction: Only for the installer. Gives access to advanced settings. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
°C °C – – Tank Additional zone Explanation – Possible actions on this screen Go through the list of the submenu. Go to the submenu. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
INFORMATION The procedures to program other schedules are similar. To program the schedule: overview Example: You want to program the following schedule: User defined 1 EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 127
1 Select the day of which you want to clear the content. For example Friday User defined 1 2 Select Delete. Delete Edit Copy 3 Select OK to confirm. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 128
To copy the schedule to the other weekdays: 1 Select Monday. User defined 1 2 Select Copy. Delete Edit Copy Result: Next to the copied day, "C" is displayed. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 129
8:00 21°C 23:00 18°C --:-- 4 Confirm the changes. 5 Select Saturday. 6 Select Copy. 7 Select Sunday. 8 Select Paste. Result: User defined 1 EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
See "9.4.4 Using weather-dependent curves" [ 133]. 9.4.2 2-points curve Define the weather-dependent curve with these two setpoints: ▪ Setpoint (X1, Y2) ▪ Setpoint (X2, Y1) Example EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Examples Weather-dependent curve when slope is selected: Weather-dependent curve when offset is selected: EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
9.4.4 Using weather-dependent curves Configure weather-dependent curves as following: To define the setpoint mode To use the weather-dependent curve, you need to define the correct setpoint mode: EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 134
To fine-tune the weather-dependent curve: slope-offset curve The following table describes how to fine-tune the weather-dependent curve of a zone or tank: EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
To display the error code, open the menu screen and go to [0] Malfunctioning. Press more information about the error. User profile Operation Malfunctioning Room Main zone EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Room frost protection, when enabled, is not guaranteed when there is no room thermostat that can activate the heat pump. This is the case when: ▪ [2.9] Control=External room thermostat and [C.2] Space heating/ cooling=Off, or if EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 137
Space heating/cooling=On, and The unit will supply leaving water to the heat emitters to heat up the room ▪ Operation mode=Heating according to normal logic. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 138
▪ Outdoor temperature drops below 6°C ▪ Space heating/cooling=On, and There is no room frost protection. ▪ Operation mode=Cooling Room thermostat control ([C‑07]=2) EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 139
Human Comfort Interface or the external room sensor cannot be installed at the ideal location. "5.7 Setting up an external temperature sensor" [ 55]). EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
▪ In Weather dependent LWT setpoint mode, the scheduled actions consist of desired shift actions, either preset or custom. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 141
131] and "9.4.3 Slope-offset curve" [ 132]. Code Description [2.E] ▪ 2-points ▪ Slope-Offset Heating WD curve Set weather-dependent heating for the main zone (if [2.4]=1 or 2): EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 142
Note: This value should be lower than [1‑02] as for high outdoor temperatures less warm water is required. Cooling WD curve Set weather-dependent cooling for the main zone (if [2.4]=2): EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 143
It is important to set Emitter type correctly and in accordance with your system layout. The target delta T for the main zone depends on it. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 144
Setpoint range To prevent a wrong (i.e. too hot or too cold) leaving water temperature for the main leaving water temperature zone, limit its temperature range. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 145
▪ Otherwise: 37°C~55°C [2.8.3] [9-02] Cooling minimum: ▪ 5°C~18°C [2.8.4] [9-03] Cooling maximum: ▪ 18°C~22°C Control Define how the operation of the unit is controlled. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 146
The difference delta T indicates, depends on the operation mode: ▪ In heating mode, delta T indicates the temperature difference between the leaving water setpoint and entering water. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 147
Additionally, also the desired leaving water temperature must be configured: if Modulation is enabled, the unit automatically calculates the desired leaving water temperature. These calculations are based on: EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 148
1 leaving water temperature zone, connect the shut-off valve to the heating/cooling output. The shut off valve for the main leaving water temperature zone can close under these circumstances: EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
▪ 1 Yes: closes when the space operation mode is cooling. 9.5.4 Additional zone Overview The following items are listed in the submenu: EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 150
126]. Setpoint mode The setpoint mode of the additional zone can be independently set from the setpoint mode of the main zone. "Setpoint mode" [ 141]. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 151
Also see "9.5.3 Main zone" [ 140]. Code Description [2.E] ▪ 2-points ▪ Slope-Offset Heating WD curve Set weather-dependent heating for the additional zone (if [3.4]=1 or 2): EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 152
Note: This value should be lower than [0‑01] as for high outdoor temperatures less warm water is required. Cooling WD curve Set weather-dependent cooling for the additional zone (if [3.4]=2): EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 153
[9‑05]~[9‑06] [1‑0C] 0: Underfloor Maximum 55°C Variable (see [3.B.1]) heating 1: Fancoil unit Maximum 55°C Variable (see [3.B.1]) 2: Radiator Maximum 70°C Fixed 10°C EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 154
(X2M/35a) ▪ 2: 2 contacts. Connected to 2 digital inputs (X2M/34a and X2M/35a) Leaving water temperature: Delta T For more information, see "9.5.3 Main zone" [ 140]. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
To tell the system which space operation to use, you can: You can… Location Check which space operation mode is currently used. Home screen EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 156
Cooling only: Restricted 4 Confirm the changes. Example: Changeover restrictions When Restriction During cold season. Heating only Example: October, November, December, January, February and March. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 157
(thus 24+1=25°C) and the desired heating temperature added by the offset value (thus 22+4=26°C). EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 158
LWT zone. Code Description [4.4] [7‑02] ▪ 0: Single zone Only one leaving water temperature zone: a Main LWT zone EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 159
When the space heating/cooling operation is OFF, the pump is always OFF. When space heating/cooling operation is ON, you have the choice between these operation modes: EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 160
Sample is ONLY available in leaving water temperature control. a Space heating/cooling control b Off c On d LWT temperature e Actual f Desired g Pump operation EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 161
With this limitation range, delta T is possible and the comfort is guaranteed. The maximum values depend on the unit type: EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 162
Use this setting to compensate for possible heat losses of the building due to the evaporation of melted ice or snow. (e.g. in cold region countries). EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Room frost protection [1.4] prevents the room from getting too cold. For more information about room frost protection, see "9.5.2 Room" [ 136]. 9.5.6 Tank Overview The following items are listed in the submenu: EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 164
When you later want to change the storage setpoint, you only have to do it in one place. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 165
▪ 2: Schedule only: The domestic hot water tank can ONLY be heated according to a schedule. See the operation manual for more details. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 166
[5.7.5] [2‑04] Duration 5~60 minutes [2-03] [2-04] 00.00 01.00 22.00 23.00 24.00 [2-02] Domestic hot water temperature User setpoint temperature High setpoint temperature [2-03] t Time EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 167
During disinfection of the domestic hot water tank, the DHW temperature can exceed this maximum temperature. INFORMATION Limit the maximum hot water temperature according to the applicable legislation. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 168
(according to the weather dependent curve), the storage economic and reheat temperature are NOT weather dependent. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 169
BUH OFF HP MAX [6-01] [6-00] HP OFF HP ON = 60°C = 50°C HP MAX [6-01] = 2°C [6-00] = 2°C BUH Backup heater EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
[7.3] Holiday [7.4] Quiet [7.5] Electricity price [7.6] Gas price Language Code Description [7.1] Language Time/date Code Description [7.2] Set the local time and date EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 171
You can use quiet mode to decrease the sound of the outdoor unit. However, this also decreases the heating/cooling capacity of the system. There are multiple quiet mode levels. The installer can: EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 172
Only applicable in combination with the bivalent function. See also "Bivalent" [ 192]. Code Description [7.5.1] Electricity price > High [7.5.2] Electricity price > Medium [7.5.3] Electricity price > Low [7.6] Gas price EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 173
An incentive can be taken into account when setting the energy prices. Although the running cost can increase, the total operation cost, taking into account the reimbursement will be optimized. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Electricity price=12.49+5 Electricity price=17.49 Price Value in breadcrumb Gas: 4.08 /kWh [7.6]=8.6 Electricity: 12.49 /kWh [7.5.1]=17 9.5.8 Information Overview The following items are listed in the submenu: EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 175
Status/mode of each actuator Example: Domestic hot water pump ON/OFF [8.6] Operation modes Current operation mode Example: Defrost/oil return mode [8.7] About Version information about the system EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
To restart the configuration wizard, go to Installer settings > Configuration wizard [9.1]. Domestic hot water This part only applies to systems with an optional domestic hot water tank installed. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 177
▪ 2: Disinfection: Installed for disinfection. It runs when the disinfection function of the domestic hot water tank is running. No further settings are needed. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 178
1-step only backup heater or a backup heater with 2 steps. If 2 steps, the capacity of the second step depends on this setting. It can also be chosen to have a higher capacity of the second step in emergency. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 179
Only for systems with integrated domestic hot water tank: If the storage temperature setpoint is higher than 50°C, Daikin recommends NOT to disable the backup heater second step because it will have a big impact on the required time for the unit to heat up the domestic hot water tank.
Page 180
Two actions per day are allowed in a week schedule. For more information, see "9.3.7 Schedule screen: Example" [ 126]. Example: Only allow the booster heater to operate during the night. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 181
<[5‑03] and [5‑02]=1. The domestic hot water temperature can be maximum the heat pump OFF temperature. [9.4.4] [4-03] ▪ 1: Booster heater operation is allowed when required. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 182
To manually recover it via the user interface, go to the Malfunctioning main menu screen and confirm whether the backup heater and/or booster heater can take over the heat load or not. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 183
This is important in case glycol is used to protect the water circuit against freezing. If NOT set correctly, the liquid in the piping can freeze. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 184
Range: 0°C~20°C Timers for simultaneous space and domestic hot water operation request [8-02]: Anti-recycle timer EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 185
This preset value is always taken into account. Range: 5~95 minutes Remark: It is NOT allowed to set [8‑01] to a value below 10 minutes. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 186
Therefore, always enable the auto restart function. ▪ 3 Safety thermostat: A safety thermostat is connected to the system (normal closed contact) EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 187
▪ 0 Amp: The limitation values are set in A. ▪ 1 kW: The limitation values are set in kW. Limit when [9.9.1]=Continuous and [9.9.2]=Amp: EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 189
(BBR16 activation and BBR16 power limit). After 2 weeks, the unit freezes these settings. Note: This is different from the permanent power limitation, which is always changeable. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 191
The outdoor temperature is averaged over the selected time period. Code Description [9.B.3] [1-0A] Averaging time: ▪ 0: No averaging ▪ 1: 12 hours ▪ 2: 24 hours ▪ 3: 48 hours ▪ 4: 72 hours EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 192
Space heating by the heat Bivalent signal for the pump system… auxiliary boiler is… Drops below T Stops Active calc Rises above T +3°C Starts Inactive calc EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 193
2 Determine the value of [C‑03] using the graph: 2.5 (a) 10.5 (b) Example: a [C‑03]=2.5 in case of COP=3 and LWT=35°C b [C‑03]=10.5 in case of COP=3 and LWT=55°C EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 194
See also table below (Alarm output logic). Alarm output logic [C-09] Alarm No alarm No power supply to unit Closed output Open output Open output Open output Closed output EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 195
To enable the power saving function setting, [E‑08] needs to be enabled on the user interface. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 196
▪ To export MMI settings 1 Open the front panel (1) and the user interface panel (2) (see — "6.2.5 To open the indoor unit" [ 63]): EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
[C.2] Space heating/cooling Malfunctioning Room [C.3] Tank To enable or disable functionalities In the operation menu, you can separately enable or disable functionalities of the unit. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 198
[C.1] Room ▪ 0: Off ▪ 1: On [C.2] Space heating/cooling ▪ 0: Off ▪ 1: On [C.3] Tank ▪ 0: Off ▪ 1: On EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
(*) Only applicable for reversible models, or heating only models + conversion kit (**) Only accessible by installer INFORMATION Depending on the selected installer settings and unit type, settings will be visible/ invisible. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Solar kit settings are shown but are NOT applicable for this unit. Settings shall NOT be used or changed. INFORMATION Depending on the selected installer settings and unit type, settings will be visible/ invisible. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
10 Commissioning NOTICE General commissioning checklist. Next to the commissioning instructions in this chapter, a general commissioning checklist is also available on the Daikin Business Portal (authentication required). The general commissioning checklist is complementary to the instructions in this chapter and can be used as a guideline and reporting template during the commissioning and hand-over to the user.
There are NO damaged components or squeezed pipes on the inside of the indoor and outdoor units. Backup heater circuit breaker F1B (field supply) is turned ON. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
— reach the minimum required flow rate + 2 l/min. During pump test run, the unit can operate below the minimum required flow rate. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
3 In the menu, set Type = Manual. 4 Select Start air purge. 5 Select OK to confirm. Result: The air purge starts. It stops automatically when ready. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
"To change — the user permission level" [ 117]. 2 Go to [A.1]: Commissioning > Operation test run. 3 Select a test from the list. Example: Heating. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
2 Select OK to confirm. Possible actuator test runs ▪ Booster heater test ▪ Backup heater 1 test ▪ Backup heater 2 test ▪ Pump test EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
2 the desired leaving water temperature, up to 55°C. Example: 24h (1) 36h (2) 35°C (2) 25°C (1) T Desired leaving water temperature (15~55°C) t Duration (1~72 h) EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 208
[D‑01]=0 ▪ [4‑08]=0 ▪ [4‑01]≠1 Steps Conditions: An underfloor heating screed dryout schedule has been programmed. "To program an underfloor heating screed dryout schedule" [ 207]. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 209
1 Go to [A.4.3]: Commissioning > UFH screed dryout > Status 2 You can read out the value here: Stopped at + the step — where the underfloor screed dryout was stopped. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 210
If the UFH screed dryout program was stopped due to a power failure and the power resumes, the program will automatically restart the last implemented step. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Show the user what to do for the maintenance of the unit. ▪ Explain the user about energy saving tips as described in the operation manual. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Before performing any maintenance or service work, touch a metal part of the unit in order to eliminate static electricity and to protect the PCB. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Pressure relief valve of the domestic hot water tank ▪ Switch box 12.3.4 Yearly maintenance indoor unit: instructions Water pressure Keep water pressure above 1 bar. If it is lower, add water. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 214
"12.4.3 To install the water filter" [ 217] Water pressure relief valve Open the valve and check if it operates correctly. The water may be very hot! Checkpoints are: EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
▪ "12.4.1 To remove the water filter" [ 216] ▪ "12.4.2 To clean the water filter in case of trouble" [ 216] ▪ "12.4.3 To install the water filter" [ 217] EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Opening the magnetic filter/dirt separator is ONLY required in case of severe issues. Preferably this action is never to be done during the complete lifetime of the magnetic filter/dirt separator. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Check the condition of the O-rings and replace if needed. Apply water to the O-rings before installation. 1 Install the water filter in the correct location. a Clip b Magnetic filter/dirt separator EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 218
Make sure to open the valve (if equipped) towards the expansion vessel, otherwise the overpressure will be generated. 5 Open the stop valves and add water to the water circuit if needed. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
If you are unable to find the cause of the problem, call your dealer. DANGER: RISK OF ELECTROCUTION EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Make sure that the water volume in the too low installation is above the minimum required value (see "7.1.3 To check the water volume and flow rate" [ 78]). EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
We recommend to purge air with the air purge function of the unit (to be performed by the installer). If you purge air from the heat emitters or collectors, mind the following: EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Purge air manually (see "To perform a manual air purge" [ 204]) or use the automatic air purge function (see "To perform an automatic air purge" [ 205]). EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
▪ If the water keeps running out of the unit, close both the water inlet and outlet shut-off valves first and then contact your dealer. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
13.4.1 To display the help text in case of a malfunction In case of a malfunction, the following will appear on the home screen depending on the severity: EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Overheating water circuit (thermostat) A1-00 Zero cross detection problem A5-00 OU: High pressure peak cut / freeze protection problem AA-01 Backup heater overheated AC-00 Booster heater overheated EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 227
OU: Malfunction of compressor input (CT) system H9-00 OU: Malfunction of outdoor air thermistor HC-00 Tank temperature sensor problem HC-01 Second tank temperature sensor problem EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 228
OU: Defect of power supply voltage U3-00 Underfloor heating screed dryout function not completed correctly U4-00 Indoor/outdoor unit communication problem U5-00 User interface communication problem EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 229
If an U8‑04 error occurs, the error can be reset after a successful update of the software. If the software is not successfully updated then you must make sure that your USB device has the FAT32 format. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 230
A malfunctioning booster heater will have an impact on energy metering and power consumption control. INFORMATION The user interface of the indoor unit will display how to reset an error code. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
See: ▪ "6.3.6 To install the discharge grille" [ 69] ▪ "6.3.7 To remove the discharge grille, and put the grille in safety position" [ 70] EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 232
3 Turn the EEV magnet clockwise to the fully open position of the valve. If you are not sure about what the open position is, turn the valve in its middle position so that refrigerant can pass. EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Technical data 15 Technical data A subset of the latest technical data is available on the regional Daikin website (publicly accessible). The full set of latest technical data is available on the Daikin Business Portal (authentication required). In this chapter 15.1...
Right side view See note *** See note *** Notes: Symbols: Live Neutral Protective earth Noiseless earth Field wiring Option Terminal strip Terminal Connector Connection EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 239
Light-emitting diode (service monitor is orange) HAP (A1P) Light-emitting diode (service monitor is green) K1R (A1P) Magnetic relay (Y1S) K1R (A4P) Magnetic relay (E1HHEX~E3HHEX) K2R (A1P) Magnetic relay (Y2S) EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 245
Switch box (6) Field supplied options (6) Field supplied options 12 V DC pulse detection (voltage 12 V DC pulse detection (voltage supplied by PCB) supplied by PCB) EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 246
Only for heat pump convector Only for wired On/OFF thermostat Only for wired On/OFF thermostat Only for wireless On/OFF thermostat Only for wireless On/OFF thermostat EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Page 247
& add: X2M: 3-4 Only for Human Comfort Interface 2 core 2×0.75 X5M: 11-12 A14P: P1-P2 user interface communication 2 core 2×0.75 A13P: P1-P2 LAN adapter communication 4D124706 EPRA14~18DAV3+W1 + ETBH/X16DA6V+9W Installer reference guide Daikin Altherma 3 H HT W 4P587501-1 – 2019.07...
Optional equipment Equipment made or approved by Daikin that can be combined with the product according to the instructions in the accompanying documentation. Field supply Equipment NOT made by Daikin that can be combined with the product according to the instructions in the accompanying documentation.
Page 250
2/11 Field settings table Installer setting at variance with default value Breadcrumb Field code Setting name Range, step Date Official Value Default value Room └─ Antifrost 1.4.1 [2-06] Activation 0: Disabled 1: Enabled 1.4.2 [2-05] Room setpoint 4~16°C, step: 1°C 8°C └─...
Page 251
3/11 Field settings table Installer setting at variance with default value Breadcrumb Field code Setting name Range, step Date Official Value Default value └─ Heating WD curve [0-00] Leaving water value for high ambient temp. for LWT add zone heating WD curve. [9-05]~min(45,[9-06])°C, step: 1°C [2-0C]=0 25°C...
Page 252
4/11 Field settings table Installer setting at variance with default value Breadcrumb Field code Setting name Range, step Date Official Value Default value └─ Disinfection 5.7.1 [2-01] Activation 0: No 1: Yes 5.7.2 [2-00] Operation day 0: Each day 1: Monday 2: Tuesday 3: Wednesday 4: Thursday...
Page 253
5/11 Field settings table Installer setting at variance with default value Breadcrumb Field code Setting name Range, step Date Official Value Default value 9.1.4.4 [6-04] Additional capacity step 2 0~10kW, step: 0,2kW 4kW (*1) 6kW (*2) └─ Main zone 9.1.5.1 [2-0C] Emitter type 0: Underfloor heating...
Page 254
6/11 Field settings table Installer setting at variance with default value Breadcrumb Field code Setting name Range, step Date Official Value Default value 9.2.1 [E-05] Domestic hot water No DHW (*3) [E-06] EKHW (*3) [E-07] Integrated (*4) EKHWP (*3) 9.2.2 [D-02] DHW pump 0: No DHW pump...
Page 255
7/11 Field settings table Installer setting at variance with default value Breadcrumb Field code Setting name Range, step Date Official Value Default value 9.9.B [5-0B] Limit 3 0~20 kW, step: 0,5 kW 20 kW 9.9.C [5-0C] Limit 4 0~20 kW, step: 0,5 kW 20 kW 9.9.D [4-01]...
Page 256
8/11 Field settings table Installer setting at variance with default value Breadcrumb Field code Setting name Range, step Date Official Value Default value [1-02] Leaving water value for low ambient temp. for LWT main zone heating WD curve. [9-01]~[9-00], step: 1°C [2-0C]=0 35°C [2-0C]=1...
Page 257
9/11 Field settings table Installer setting at variance with default value Breadcrumb Field code Setting name Range, step Date Official Value Default value [4-01] Which electric heater has priority? 0: None 1: BSH 2: BUH [4-02] Below which outdoor temperature is heating allowed? 14~35°C, step: 1°C 35°C [4-03]...
Page 258
10/11 Field settings table Installer setting at variance with default value Breadcrumb Field code Setting name Range, step Date Official Value Default value [7-03] [7-04] [7-05] Boiler efficiency 0: Very high 1: High 2: Medium 3: Low 4: Very low [7-06] HP Forced OFF 0: Disabled...
Page 259
11/11 Field settings table Installer setting at variance with default value Breadcrumb Field code Setting name Range, step Date Official Value Default value [D-01] Contact type of preferential kWh rate PS installation? 0: No 1: Active open 2: Active closed 3: Safety thermostat [D-02] Which type of DHW pump is installed?
Page 260
4P587501-1 2019.07 Verantwortung für Energie und Umwelt...