Installation manual Daikin Altherma 3 H HT W https://daikintechnicaldatahub.eu ETBH16DF6V ETBH16DF9W Installation manual ETBX16DF6V English Daikin Altherma 3 H HT W ETBX16DF9W...
Slope-offset curve ............23 Latest revisions of the supplied documentation may be available on 6.3.4 Using weather-dependent curves ....... 24 the regional Daikin website or via your dealer. Settings menu ................24 The original documentation is written in English. All other languages 6.4.1 Main zone ..............
▪ A subset of the latest technical data is available on the regional Daikin website (publicly accessible). Unit installation ▪ The full set of latest technical data is available on the Daikin Business Portal (authentication required). Preparing the installation site...
2 Reinstall the switch box cover and close the switch box. 3 Reinstall the front panel. NOTICE When closing the indoor unit cover, make sure that the tightening torque does NOT exceed 4.1 N•m. ETBH/X16DF6V+9W Installation manual Daikin Altherma 3 H HT W 4P586453-1C – 2020.10...
To check the water volume and flow rate Minimum water volume Check that the total water volume in the installation is minimum 20 litres, the internal water volume of the outdoor unit NOT included. Installation manual ETBH/X16DF6V+9W Daikin Altherma 3 H HT W 4P586453-1C – 2020.10...
4.2.2 To fill the water circuit To fill the water circuit, use a field supply filling kit. Make sure you comply with the applicable legislation. ETBH/X16DF6V+9W Installation manual Daikin Altherma 3 H HT W 4P586453-1C – 2020.10...
Adding glycol to the water circuit reduces the maximum allowed water volume of the system. For more information, see the installer reference guide (topic "To check the water volume and flow rate"). Installation manual ETBH/X16DF6V+9W Daikin Altherma 3 H HT W 4P586453-1C – 2020.10...
For the additional zone: ▪ [3.A] Thermostat type Only for the backup heater of the indoor unit ▪ [3.9] (read-only) Control supply" [ 4 12]. "5.3.2 To connect the backup heater power ETBH/X16DF6V+9W Installation manual Daikin Altherma 3 H HT W 4P586453-1C – 2020.10...
Page 10
Maximum length: 500 m adapter [2.9] Control ▪ Addendum book optional [1.6] Room sensor offset equipment Wires: 2×(0.75~1.25 mm²). Must be sheathed. Maximum length: 200 m See below ("LAN adapter – System requirements"). Installation manual ETBH/X16DF6V+9W Daikin Altherma 3 H HT W 4P586453-1C – 2020.10...
In case of normal kWh rate power supply Interconnection Wires: (3+GND)×1.5 mm² cable (= main power supply) — 10 9 1 2 3 1N~, 50 Hz, 230 V AC, 6.3 A 1 2 3 ETBH/X16DF6V+9W Installation manual Daikin Altherma 3 H HT W 4P586453-1C – 2020.10...
CAUTION To guarantee the unit is completely earthed, always connect the backup heater power supply and the earth cable. Installation manual ETBH/X16DF6V+9W Daikin Altherma 3 H HT W 4P586453-1C – 2020.10...
L1 L2 L3 400 V AC NOTICE Do NOT cut or remove the backup heater power supply cable. 3 Fix the cable with cable ties to the cable tie mountings. ETBH/X16DF6V+9W Installation manual Daikin Altherma 3 H HT W 4P586453-1C – 2020.10...
DHW pump output. Maximum load: 2 A (inrush), 230 V AC, A4P Installation of EKRP1HBAA is 1 A (continuous) required. [9.2.2] DHW pump [9.2.3] DHW pump schedule unit" [ 4 5]): 1 Open the following (see "3.2.1 To open the indoor Installation manual ETBH/X16DF6V+9W Daikin Altherma 3 H HT W 4P586453-1C – 2020.10...
2 Switch box cover 3 Switch box 2 Connect the changeover to external heat source cable to the appropriate terminals as shown in the illustration below. ETBH/X16DF6V+9W Installation manual Daikin Altherma 3 H HT W 4P586453-1C – 2020.10...
3 Switch box appropriate terminals as shown in the illustration below. 2 Connect the safety thermostat (normally closed) cable to the appropriate terminals as shown in the illustration below. Installation manual ETBH/X16DF6V+9W Daikin Altherma 3 H HT W 4P586453-1C – 2020.10...
4 26] ▪ "6.5 Menu structure: Overview installer 6.1.1 To access the most used commands To change the user permission level You can change the user permission level as follows: ETBH/X16DF6V+9W Installation manual Daikin Altherma 3 H HT W 4P586453-1C – 2020.10...
(User field settings. settings > Time/date) once the unit is initialised. 6.2.3 Configuration wizard: System Indoor unit type The indoor unit type is displayed, but cannot be adjusted. Installation manual ETBH/X16DF6V+9W Daikin Altherma 3 H HT W 4P586453-1C – 2020.10...
Page 19
Main LWT zone and the booster heater in the optional tank takes over the domestic hot water production. ETBH/X16DF6V+9W Installation manual Daikin Altherma 3 H HT W 4P586453-1C – 2020.10...
50°C, metering and/or power consumption control feature to work properly. Daikin recommends NOT to disable the backup heater When measuring the resistance value of the booster heater, you can second step because it will have a big impact on the...
"6.2.5 Configuration zone" [ 4 21]. wizard: Main ▪ Enable leaving water temperature modulation and increase the maximum modulation [2.C]. Control Define how the operation of the unit is controlled. ETBH/X16DF6V+9W Installation manual Daikin Altherma 3 H HT W 4P586453-1C – 2020.10...
Because it reacts more quickly, it prevents high rises and drops of the indoor temperature and water temperature at tap points. Advantage Weather-dependent operation reduces energy consumption. Installation manual ETBH/X16DF6V+9W Daikin Altherma 3 H HT W 4P586453-1C – 2020.10...
The icon corresponds to the heat emitter temperature at X2. for that zone: Slope ▪ : Underfloor heating Offset ▪ : Fan coil unit ▪ : Radiator ▪ : Domestic hot water tank ETBH/X16DF6V+9W Installation manual Daikin Altherma 3 H HT W 4P586453-1C – 2020.10...
To change the weather-dependent curve Thermostat type Zone Go to … Only applicable in external room thermostat control. Main zone – Heating [2.5] Main zone > Heating WD curve Installation manual ETBH/X16DF6V+9W Daikin Altherma 3 H HT W 4P586453-1C – 2020.10...
▪ 2: 2 contacts 6.4.3 Information Dealer information The installer can fill in his contact number here. Code Description [8.3] Number that users can call in case of problems. ETBH/X16DF6V+9W Installation manual Daikin Altherma 3 H HT W 4P586453-1C – 2020.10...
Solar kit settings are shown but are NOT applicable for this unit. Settings shall NOT be used or changed. INFORMATION Depending on the selected installer settings and unit type, settings will be visible/invisible. Installation manual ETBH/X16DF6V+9W Daikin Altherma 3 H HT W 4P586453-1C – 2020.10...
Next commissioning instructions in this chapter, a general ▪ Between the local supply panel and the indoor unit commissioning checklist is also available on the Daikin ▪ Between the indoor unit and the valves (if applicable) Business Portal (authentication required).
1 Go to Stop UFH screed dryout. To monitor the temperatures: 2 Select OK to confirm. 1 In the menu, go to Sensors. 2 Select the temperature information. Installation manual ETBH/X16DF6V+9W Daikin Altherma 3 H HT W 4P586453-1C – 2020.10...
▪ Show the user what to do for the maintenance of the unit. ▪ Explain the user about energy saving tips as described in the operation manual. ETBH/X16DF6V+9W Installation manual Daikin Altherma 3 H HT W 4P586453-1C – 2020.10...
9 Technical data Technical data A subset of the latest technical data is available on the regional Daikin website (publicly accessible). The full set of latest technical data is available on the Daikin Business Portal (authentication required). Piping diagram: Indoor unit...
Ext. thermistor External thermistor Terminal strip Heat pump convector Heat pump convector Optional Field supply Position in switch box English Translation Position in switch box Position in switch box ETBH/X16DF6V+9W Installation manual Daikin Altherma 3 H HT W 4P586453-1C – 2020.10...
Page 32
Shut-off valve Switch box (7) Option PCBs (7) Option PCBs Alarm output Alarm output Changeover to ext. heat source Changeover to external heat source Max. load Maximum load Installation manual ETBH/X16DF6V+9W Daikin Altherma 3 H HT W 4P586453-1C – 2020.10...
Page 33
A11P: X5: 4-5 5 core 2×0.75 A20P: J2 X5M: 11-12 A14P: P1-P2 user interface communication communication A11P: X9: 1-2-3 2 core 2×0.75 A13P: P1-P2 LAN adapter communication 4D124706A ETBH/X16DF6V+9W Installation manual Daikin Altherma 3 H HT W 4P586453-1C – 2020.10...
Page 36
4P586453-1 C 00000003 4P586453-1C 2020.10 Verantwortung für Energie und Umwelt...