Nibe S1256PC Installer Manual page 60

Ground source heat pump
Hide thumbs Also See for S1256PC:
Table of Contents

Advertisement

TIP
The cooling module is installed in reverse order.
NOTE
During reassembly, the enclosed O-rings should
replace the existing ones on the shut-off valves
(EP14-QM32), (EP14-QM33) and (EP14-QM34).
60
Chapter 10 | Service
XF22
XF2
XF11
USB SERVICE OUTLET
When a USB memory is connected, a new menu (menu 8)
appears in the display.
Menu 8.1 - "Update the software"
You can update the software with a USB memory in menu
8.1 - "Update the software".
NOTE
In order to update using a USB memory, the
memory must contain a file with software for
S1256PC from NIBE.
Software for S1256PC can be downloaded from
https://myuplink.com.
One or more files are shown in the display. Select a file and
press "OK".
TIP
A software update does not reset the menu set-
tings in S1256PC.
Caution
If the update is interrupted before it is complete
(e.g. during a power cut), the software is automat-
ically restored to the previous version.
Menu 8.2 - Logging
Setting range: 1 s – 60 min
Here you can choose how current measurement values from
S1256PC should be saved onto a log file on the USB memory.
1.
Set the desired interval between loggings.
2.
Select "Start logging".
3. The relevant measurement values from S1256PC are
now saved in a file on the USB memory at the set interval
until you select "Stop logging".