Nibe S1256PC Installer Manual page 23

Ground source heat pump
Hide thumbs Also See for S1256PC:
Table of Contents

Advertisement

TIP
Some of the following functions can also be activ-
ated and scheduled via menu settings.
Selectable inputs
Selectable inputs on the base board (AA2) for these func-
tions are AA2-X28:3-11. Each function connects to any input
and GND (AA2-X29).
S1256PC External
AA2-X28
3
8
4
5
6
7
AA2-X29
GND
The example above uses the inputs AUX1 (AA2-X28:3) and AUX2 (AA2-X28:4).
Selectable outputs
A selectable output is AA2-X27.
The output is a potential-free switching relay.
If S1256PC is switched off or in emergency mode, the relay
is in C-NC position.
AA2-X27
NO
3
C
K10
2
NC
1
S1256PC
External
Caution
The relay output may be subjected to a max load
of 2 A at resistive load (230 V~).
TIP
The AXC accessory is required if more than one
function is to be connected to the AUX output.
1 (Accessory NV10)
NIBE S1256PC
Possible selection for AUX inputs
Temperature sensor
Available options are:
it is possible to connect two own sensors (BT37.1, BT37.2).
cooling/heating (BT74), determines when it is time to
switch between cooling and heating mode.
external return line sensor (BT71)
displayed hot water sensor for HWC (BT70). Placed on the
supply line.
displayed hot water sensor for HWC (BT82). Placed on the
return line.
Monitor
Available options are:
alarm from external units.
The alarm is connected to the control, which means that
the malfunction is shown as an information message in
the display. Potential free signal of type NO or NC.
pressure switch for climate system (NC).
1
level monitor
/ pressure switch / flow monitor for brine
(NC).
External activation of functions
An external switch function can be connected to S1256PC
to activate various functions. The function is activated
during the time the switch is closed.
Possible functions that can be activated:
forced control of brine pump
hot water demand mode "More hot water"
hot water demand mode "Small"
"External adjustment"
When the switch is closed, the temperature is changed in
°C (if a room sensor is connected and activated). If a room
sensor is not connected or not activated, the desired
change of "Temperature" ("Offset") is set with the number
of steps selected. The value is adjustable between -10
and +10. External adjustment of zones 2 to 4 requires ac-
cessories.
zones 1 to 4
Setting the value for the change is performed in menu
1.30.3 - "External adjustment".
activation of one of four fan speeds.
(Can be selected if ventilation accessory is activated.)
The following options are available:
"Activate fan speed 1 (NO)" - "Activate fan speed 4 (NO)"
"Activate fan speed 1 (NC)"
Chapter 5 | Electrical connections