Nibe S1256PC Installer Manual page 41

Ground source heat pump
Hide thumbs Also See for S1256PC:
Table of Contents

Advertisement

MENU 2.5 - HOT WATER CIRCULATION
Operating time
Setting range: 1 – 60 min
Downtime
Setting range: 0 – 60 min
Period
Active days
Setting range: Monday – Sunday
Start time
Setting range: 00:00 – 23:59
Stop time
Setting range: 00:00 – 23:59
Set hot water circulation for up to five periods per day here.
During the set periods, the hot water circulation pump will
run according to the settings above.
"Operating time" decide how long the hot water circulation
pump must run per operating instance.
"Downtime" decide how long the hot water circulation pump
must be stationary between operating instances.
"Period" Here, you set the period of time during which the
hot water circulation pump will run, by selecting Active days,
Start time and Stop time.
NOTE
Hot water circulation is activated in menu 7.4
"Selectable in/outputs" or via accessory.
NIBE S1256PC
Chapter 9 | Control - Menus
41