Installation
The following steps must be followed when installing each of these modules:
1.
Remove all power (AC and DC) from the FACP before installing the modules.
2.
Cut jumper JP1 (for connectors J3 and J5) and/or JP2 (for connectors J4 and J6) on the main
circuit board to allow the control panel to supervise the placement of any installed option
module.
3.
Install the two supplied metal standoffs in the locations indicated. These standoffs provide the
required earth ground protection.
4.
Carefully plug the connectors on the option module into connectors J3 and J5 or J4 and J6 on
the FACP main circuit board, being careful not to bend any pins.
5.
Secure the option module to the standoff on the main circuit board with the supplied screws.
6.
When the installation has been completed, connect the wiring to the modules as indicated in
the following sections.
7.
Test system for proper operation.
+
-
+
-
B+ B-
Nonreset Reset
NAC 1
J9
J7
HOT NEUT EARTH

4XTMF Transmitter Module Installation

The 4XTMF provides a supervised output for a local energy municipal box transmitter in addition
to alarm and trouble reverse polarity. A jumper option allows the reverse polarity circuit to open
with a system trouble condition if no alarm condition exists. A disable switch allows disabling of
the transmitter output during testing to prevent accidental calling of the monitoring service.
Local Energy Municipal Box Service (NFPA 72 Auxiliary Fire Alarm Systems):
Supervisory Current: 5.0 mA
Trip Current: 350 mA (subtracted from notification appliance power)
Coil Voltage: 3.65 VDC
26
B+
B-
B+
B-
B+
B-
B+
B-
B+
ZONE 1 ZONE 2
ZONE 3 ZONE 4
NAC 2
CLASS A
CONVERTER
ZONE 1
FIRE ALARM
SUPERVISORY
TROUBLE
ZONE 2
FIRE ALARM
SUPERVISORY
TROUBLE
ZONE 3
FIRE ALARM
SUPERVISORY
TROUBLE
ZONE 4
FIRE ALARM
SUPERVISORY
TROUBLE
NAC
AC
NAC
ZONE
SYSTEM
POWER
FAULT
POWER
DISABLE
DISABLE
TROUBLE
TROUBLE
ALARM
ACK
RESET
SILENCE
ZONE
ENABLE/DISABLE
3
1
2
TB8
EARTH BATT CHG
J8
BATTERY
JP2 Jumper
Cut to install module on J4 & J6
Figure 2.12 4X Option Module Connection to Flex 404
B-
C TRBL NORM
C
NC NO
C
ALARM
SUPV
TROUBLE
J1
J3
MAINTENANCE
J5
MAINTENANCE
MAINTENANCE
MAINTENANCE
ALARM
WALK
SILENCE
TEST
WALK
TEST
4
J4
J6
JP1
JP2
SW1
SW2 SW3
Flex 402 & Flex 404 Instruction Manual — P/N 52194:D4 3/27/2015
Installation of Optional Modules
NC NO
JP3
Standoffs
(when using
J3
J3 & J5
J5
Standoffs
(when using
J4 & J6
J4
J6
JP1 Jumper
Cut to install
module on J3 & J5

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fci gamewell flex 402

Table of Contents