Operating instructions
DALI-2 gateway Colour 1-gang
Art. no. 300641SDA2R
DALI-2 gateway Colour 2-gang
Art. no. 301281SDA2R
ALBRECHT JUNG GMBH & CO. KG
Volmestraße 1
58579 Schalksmühle
GERMANY
Telefon: +49 2355 806-0
Telefax: +49 2355 806-204
kundencenter@jung.de
04.08.2023
82406603 j0082406603
www.jung.de

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 300641SDA2R and is the answer not in the manual?

Questions and answers

Summary of Contents for Jung 300641SDA2R

  • Page 1 Operating instructions DALI-2 gateway Colour 1-gang Art. no. 300641SDA2R DALI-2 gateway Colour 2-gang Art. no. 301281SDA2R ALBRECHT JUNG GMBH & CO. KG Volmestraße 1 58579 Schalksmühle GERMANY Telefon: +49 2355 806-0 Telefax: +49 2355 806-204 kundencenter@jung.de 04.08.2023 82406603 j0082406603 www.jung.de...
  • Page 2: Table Of Contents

    DALI-2 gateway Colour 1-gang, DALI-2 gateway Colour 2-gang Table of contents Safety instructions ...................... 3 Function .......................... 3 Operation ..........................  5 Information for electrically skilled persons ................  8 Mounting and electrical connection................  8 Commissioning ......................  9 Appendix.........................  12 Technical data......................  12 Troubleshooting ....................
  • Page 3: Safety Instructions

    The device can be updated. Firmware can be easily updated with the Jung ETS Ser- vice App (additional software). The device is KNX Data Secure capable. KNX Data Secure offers protection against manipulation in building automation and can be configured in the ETS project.
  • Page 4 DALI-2 gateway Colour 1-gang, DALI-2 gateway Colour 2-gang – Control of max. 2x 64 DALI devices in max. 2x 32 groups ("2-fold" device vari- ant) – Setting the colour temperature or light colour (RGB, RGBW) for luminaires with DALI Device Type 8 in accordance with IEC 62386-209 –...
  • Page 5: Operation

    DALI-2 gateway Colour 1-gang, DALI-2 gateway Colour 2-gang Operation Image 1: DALI Gateway control panel, 1fold Image 2: DALI Gateway control panel, 2fold Button ǃ – Manual operation LED ǃ – On: Continuous manual mode active LED ǃ – Flashing: Temporary manual mode is active DŽ...
  • Page 6 DALI-2 gateway Colour 1-gang, DALI-2 gateway Colour 2-gang (10) Change-over button DALI system 1/2 (only with "2fold" device variant) If the display (8) shows bc (broadcast operation), all devices of a DALI system are controlled jointly. This is done in the following operating conditions. –...
  • Page 7 DALI-2 gateway Colour 1-gang, DALI-2 gateway Colour 2-gang ■ Press the c (1) button briefly as many times as necessary until the display (8) shows the desired group number or short address. ■ Operate output with ON/n (3) button or OFF/o (5) button. Short: switch on/off.
  • Page 8: Information For Electrically Skilled Persons

    DALI-2 gateway Colour 1-gang, DALI-2 gateway Colour 2-gang Information for electrically skilled persons Mounting and electrical connection DANGER! Electric shock when live parts are touched. Electric shocks can be fatal. Always disconnect device before carrying out work on it. For this, switch off all the corresponding circuit breakers, secure against being switched on again, and check that there is no voltage.
  • Page 9: Commissioning

    DALI-2 gateway Colour 1-gang, DALI-2 gateway Colour 2-gang Image 3: DALI gateway connection example, 2fold ■ Attach the cover cap to the bus cable connection as protection against hazard- ous voltages. If the display (8) shows Er (error), an installation fault occurred that causes mains voltage to reach the DALI cable.
  • Page 10 DALI-2 gateway Colour 1-gang, DALI-2 gateway Colour 2-gang device types, group assignments, etc.). This is the case, for example, if a device is copied unchanged in the ETS project design or a configuration tem- plate is imported. No ETS programming is possible if no mains voltage supply is connected. Safe-state mode If the device does not work properly - for instance as a result of errors in the project design or during commissioning - the execution of the loaded application program...
  • Page 11 5 s. Restoring the device to factory settings Devices can be reset to factory settings with the Jung ETS Service App. This function uses the firmware contained in the device that was active at the time of delivery (de- livered state).
  • Page 12: Appendix

    DALI-2 gateway Colour 1-gang, DALI-2 gateway Colour 2-gang Appendix Technical data KNX medium TP 256 KNX commissioning mode S mode Rated voltage KNX DC 21 ... 32 V SELV Current consumption KNX 4.5 ... 5.0 mA Connection type for bus Device connection terminal Supply Rated voltage...
  • Page 13: Troubleshooting

    DALI-2 gateway Colour 1-gang, DALI-2 gateway Colour 2-gang Image 5: Clampable cable cross-sections Installation width 72 mm / 4 HP Connection mode Screw terminal Connection torque, screw terminals max. 0.8 Nm Troubleshooting Indication shows "Er", connected DALI devices have no function, no operation possible Cause: Mains voltage on DALI cable.
  • Page 14: Warranty

    – Check and correct the programming. Warranty The warranty is provided by the specialist trade in accordance with statutory require- ments. ALBRECHT JUNG GMBH & CO. KG Volmestraße 1 58579 Schalksmühle GERMANY Telefon: +49 2355 806-0 Telefax: +49 2355 806-204 kundencenter@jung.de...