3-2. ELECTRICAL PARTS SPECIFICATIONS
Service Ref.
Symbol
Parts name
Room temperature
TH21
detection thermistor
Pipe temperature
TH22
detection thermistor/Inlet
Pipe temperature
TH23
detection thermistor/Outlet
Fuse
FUSE
(Indoor controller board)
Fan motor
MF
(with thermal fuse)
Vane motor
MV
(upper)
Power supply terminal
TB2
block
Transmission terminal
TB5
block
MA-remote controller
TB15
terminal block
*Refer to WIRING DIAGRAM for the supplied voltage.
3-3. SOUND PRESSURE LEVEL
PKFY-WL・NKMU-E
Measurement location
* Measured in anechoic room.
TCH121
Resistance 30°F/15.8 k", 50°F/9.6 k", 70°F/6.0 k", 80°F/4.8 k", 90°F/3.9 k", 100°F/3.2 k"
Resistance 30°F/15.8 k", 50°F/9.6 k", 70°F/6.0 k", 80°F/4.8 k", 90°F/3.9 k", 100°F/3.2 k"
Resistance 30°F/15.8 k", 50°F/9.6 k", 70°F/6.0 k", 80°F/4.8 k", 90°F/3.9 k", 100°F/3.2 k"
1m
PKFY-WL18NKMU-E.TH
PKFY-WL24NKMU-E.TH
PKFY-WL30NKMU-E.TH
T3.15AL250V
8 X 69W / RC0J56-AM
MSBPC20 DC12V
(L1, L2) Rated to 250V 20A *
(M1, M2, S) Rated to 250V 20A *
(1, 2) Rated to 250V 10A *
Sound pressure level at anechoic room: Low-High
Service Ref.
PKFY-WL18NKMU-E.TH
PKFY-WL24NKMU-E.TH
PKFY-WL30NKMU-E.TH
5
5
Sound pressure level dB (A)
39-42
39-45
39-49