Mitsubishi Electric CITY MULTI PKFY-WL18NKMU-E Technical & Service Manual page 39

Split-type, heat pump air conditioners
Hide thumbs Also See for CITY MULTI PKFY-WL18NKMU-E:
Table of Contents

Advertisement

11-4-2. PAR-SL101A-E
1. Press the
button
1
• If the weekly timer is enabled (
3
button
to disable it (
2. Press the
button
2
comes on and the unit enters the service mode.
.
3. Press the
button
2
B
comes on and the unit enters the test run mode.
4. Press the following buttons to start the test run.
: Switch the operation mode between cooling and heating
and start the test run.
: Switch the fan speed and start the test run.
: Switch the airflow direction and start the test run.
: Switch the louver and start the test run.
: Start the test run.
5. Stop the test run.
• Press the
button
• After 2 hours, the stop signal is transmitted.
TCH121
to stop the air conditioner.
is on), press the
is off).
for 5 seconds.
1
to stop the test run.
39
3
B
A
1
2