Up to 64 groups of units can be controlled.
The controller control transmission line can be extended to up to 1000 m.
A direct duct connection is NOT possible.
Set ON for central zone link setting.
Adapter PCB for remote control: KRP2A51 (One adapter PCB should be installed
in either the VAM or the air conditioner).
For configuration, see
"17.3.4 Linked control with more than 2
Direct duct connection system
c
a
a Controller
b Heat reclaim ventilation unit (VAM)
c Air conditioner
The VAM will operate ONLY when the air conditioner fan is on.
Other specifications are the same as those of the standard system.
For configuration, see
"17.3.5 Direct duct
All/individual control system
c
a
a
c
a
a Controller
b Heat reclaim ventilation unit (VAM)
c Air conditioner
d Central controller
Unified ON/OFF controller: DCS301B(A)51. Up to 16 groups can be controlled
(ON/OFF) by 1 controller and up to 4 controllers can be installed in 1 system.
Schedule timer: DST301B(A)51. One schedule timer can control the weekly
schedule of up to 128 units.
Adapter PCB for remote control: KRP2A51 (NOT possible to use together with
another central controller). 1 adapter PCB can control up to 64 groups
collectively.
One of the controllers must be connected to an air conditioner. However, ONLY
KRP2A51 can be connected to a VAM.
For configuration, see
"17.3.6 Central control
b
connection" [
b
d
b
system" [
4
groups" [
 76].
4
 77].
4
 78].
VAM350~2000J*VEB*
Heat reclaim ventilation unit
4P664012-1A – 2024.01