System configuration
16.4 Central control system
Installer and user reference guide
66
▪
Up to 64 groups of units can be controlled.
▪
The controller control transmission line can be extended to up to 1000 m.
▪
A direct duct connection is NOT possible.
▪
Set ON for central zone link setting.
▪
Adapter PCB for remote control: KRP2A51 (One adapter PCB should be installed
in either the VAM or the air conditioner).
For configuration, see
"17.3.4 Linked control with more than 2
Direct duct connection system
c
a
a Controller
b Heat reclaim ventilation unit (VAM)
c Air conditioner
▪
The VAM will operate ONLY when the air conditioner fan is on.
▪
Other specifications are the same as those of the standard system.
For configuration, see
"17.3.5 Direct duct
All/individual control system
c
a
a
c
a
a Controller
b Heat reclaim ventilation unit (VAM)
c Air conditioner
d Central controller
▪
Unified ON/OFF controller: DCS301B(A)51. Up to 16 groups can be controlled
(ON/OFF) by 1 controller and up to 4 controllers can be installed in 1 system.
▪
Schedule timer: DST301B(A)51. One schedule timer can control the weekly
schedule of up to 128 units.
▪
Adapter PCB for remote control: KRP2A51 (NOT possible to use together with
another central controller). 1 adapter PCB can control up to 64 groups
collectively.
▪
One of the controllers must be connected to an air conditioner. However, ONLY
KRP2A51 can be connected to a VAM.
For configuration, see
"17.3.6 Central control
b
connection" [
b
d
b
system" [
4
groups" [
76].
4
77].
4
78].
VAM350~2000J*VEB*
Heat reclaim ventilation unit
4P664012-1A – 2024.01