Linked Operation Control System; Central Control System; Installer And User Reference Guide; Configuration - Daikin VAM350J7VEB Installer And User Reference Manual

Heat reclaim ventilation unit
Hide thumbs Also See for VAM350J7VEB:
Table of Contents

Advertisement

7.3

Linked operation control system

System
Combined
1-group
operation
linked
system with
operation
VRV
control
systems
system
and Sky Air
series
Multi-group
linked
operation
control
system
Direct duct
connection
system
a
Adapter PCB for remote control
Heat reclaim ventilation unit
Air conditioner
Controller
7.4

Central control system

System
All/individual control
system
Zone control system
a
Central controller
Heat reclaim ventilation unit
Air conditioner
Controller
Controller
8

Configuration

The settings (format: XX(XX)-X-XX), e.g. 19(29)-1-02, that are used
in this chapter are composed of 3 parts, divided by "-":
VAM350~2000J7VEB
Heat reclaim ventilation unit
4P487293-1A – 2018.05
Standard method
A total of up to 16 air conditioners and heat reclaim ventilation units can be controlled.
The ventilation mode can be operated independently when air conditioners are NOT
used.
Using the local setting of the controller for air conditioners, various settings such as
precool/preheat on/off, ventilation flow rate, ventilation mode, etc. can be selected.
Since all VRV units of the installation are connected to a single communication line,
they will all be operated.
If there are problems operating all VRV units, do NOT use this system.
Up to 64 groups of units can be controlled.
The controller control transmission line can be extended to up to 1000 m.
a
A direct duct connection is NOT possible.
Set ON for central zone link setting.
Adapter PCB for remote control: KRP2A51 (One adapter PCB should be installed in
either the heat reclaim ventilation unit or the air conditioner).
The heat reclaim ventilation unit will operate ONLY when the air conditioner fan is on.
Other specifications are the same as those of the standard system.
Standard method
Unified ON/OFF controller: DCS301B(A)51. Up to 16 groups can be controlled (ON/
OFF) by 1 controller and up to 4 controllers can be installed in 1 system.
Schedule timer: DST301B(A)51. One schedule timer can control the weekly schedule
of up to 128 units.
a
Adapter PCB for remote control: KRP2A51 (NOT possible to use together with another
central controller). 1 adapter PCB can control up to 64 groups collectively.
One of the controllers must be connected to an air conditioner. (However, ONLY
KRP2A51 can be connected to a heat reclaim ventilation unit.).
Use of the central controller enables zone control via the central control line (up to 64
zones).
Central controller DCS302C(A)51, intelligent Touch Controller DCS601C51, or
a
intelligent Touch Manager DCM601A51.
A central controller can control independent operation of the heat reclaim ventilation
units in each zone.
▪ Mode number: e.g. 19(29), where 19 is the mode number for
group settings and 29 is the mode number for individual settings.
▪ Switch number: e.g. 1
▪ Position number: e.g. 02
8 Configuration
Related items in electric wiring
See
"8.3.3 1-group linked-control
system" on page 30
See
"8.3.4 Linked control with more
than 2 groups" on page 30
See
"8.3.5 Direct duct
connection" on page 31
Related items in electric wiring
See
"8.3.6 Central control
system" on page 31
See
"8.3.6 Central control
system" on page 31

Installer and user reference guide