4.10

Combustion head adjustment

At this point of the installation, the combustion head is fixed to the
boiler as shown in Fig. 18 on page 22. It is therefore especially
easy to adjust, and this adjustment depends only on the maxi-
mum output of the burner.
Turn the screw 1) (Fig. 22) until the notch matches with the front
plane 2) of the flange.
The combustion head is opened by turning the screw 1) counter-
clockwise.
The combustion head is closed by turning the screw 1) clockwise
(Fig. 24 on page 25).
The burner leaves the factory with the combu-
stion head set to notch 0.
WARNING
This adjustment allows to secure the moving parts during the
transport of the burner.
Before the burner start-up, make the adjustments according to
the required output and indicated in the diagram (Fig. 23).
NOTE:
The adjustment can be changed according to the specific
application.
1
2
20205886
Installation
RS 68/EV ULX
10
9
8
7
6
5
4
3
2
1
0
300
400
RS 120/EV ULX
10
9
8
7
6
5
20205151
4
3
2
1
0
500
600
RS 160/EV ULX
5
4
Fig. 22
3
2
1
0
900
1000
RS 200/EV ULX
5
4
3
2
1
0
1300
1400
24
GB
500
600
700
800
Max burner output (kW)
700
800
900
1000
1100
Max burner output (kW)
1100
1200
1300
1400
1500
1600
Max burner output (kW)
1500
1600
1700
1800
1900
2000
2100
Max burner output (kW)
S10260
900
1000
1100
S10261
1200
1300
1400
1500
S10351
1700
1800
1900
2000
S10352
2200
2300
2400
2500
Fig. 23