List Of Parameters - Riello RS 68/EV ULX Installation, Use And Maintenance Instructions

Forced draught gas burners
Table of Contents

Advertisement

The value 1 appears on the display screen:
P
After approx 8 seconds (it depends on the duration of the pro-
gramme), the 0 value appears on the display screen, this is to in-
dicate that the restore process has been completed correctly.
P
7.4.3

List of parameters

Parameter
No.
Description
000
INTERNAL PARAMETERS
Start backup/restore process via RDI21... / PC TOOL
(set the parameter to 1)
050
Index 0 = create backup
Index 1 = perform restore
Negative values indicate errors
Burner identification number created from the backup
055
on RDI21...
056
ASN number created by the backup on RDI21...
057
Software Version created by the backup on RDI21...
100
GENERAL PARAMETERS
102
Flame control identification date
103
Flame control identification number
104
Identification number of the group of parameters set
105
Version of the group of parameters set
107
Software version
108
Software variation
ASN number to verify the ASN number created by the
111
backup on RDI 21...
113
Burner identification
Manual setting of output
121
Not defined = automatic operation
Minimum output step position
Index 0: BACS output
123
Index 1: output of the external load regulator,
analogue.
Index 2: output of the external load regulator contacts.
Beginning flame loss test (TÜV test)(define the
124
parameter at 1)(switch of flame loss fuel valves) A
negative value indicates an error (see code 150)
Frequency of main power supply
125
0 = 50 Hz
1 = 60 Hz
126
Brightness of display
Fuel meter: Led pulse valence
128
(led pulses / volumetric flow units)
Eliminate visualisation error chronology
To eliminate the visualisation, set the parameter to 1,
130
then to 2
Answer 0: process successful
Answer -1: timeout of 1_2 - sequence
20205886
Control and display
V
h min s
%
V
h min s
%
No. of
elements
2
1
8
1
1
1
1
1
1
1
8
1
1
3
1
1
1
1
1
NOTE:
When the restore process is successfully completed, the 0
value
is
shown
Err C information: 136 D: 1 (restore process initialised) is
displayed for a brief moment.
At the end of the restore process, it is neces-
sary to check the sequence of functions and
the list of parameters.
IMPORTANT
Unit of
Values interval
Modifica-
measure-
tion
Min.
ment
-
Modification
-99
-
Reading only
0
-
Reading only
0
-
Reading only
0x100
-
Reading only
0
-
Reading only
0
-
Reading only
0
-
Reading only
0
-
Reading only
0
-
Reading only
0
-
Reading only
0
-
Modification
0
Modification /
%
0%
zero setting
%
Modification
0%
-
Modification
-6
-
Modification
0
%
Modification
0%
-
Modification
0
-
Modification
-5
48
GB
on
the
display
Degree of
Predefined
precision
setting
Max.
2
1
0; 0
99999999
1
0
127
1
0
0xFFF9
1
0
255
1
65535
1
255
1
30
0xFFFF
1
V01.08
0xFFF9
1
V03.30
225
1
1
127
1
0
99999999
1
Not defined
100%
0.1%
Not defined
0% ; 1%;
100%
0.1%
0%
1
1
0
1
1
0
100%
1%
75%
400
0,01
0
2
1
0
screen.
Access mode
Service mode
Service mode
Service mode
Service mode
Info mode
Info mode
Info mode
Info mode
Info mode
Info mode
Service mode
Info Mode
with password
Service Mode
Info mode
Service mode
Service mode
Service Mode
Service Mode
Service Mode
Service Mode

Advertisement

Table of Contents
loading

Table of Contents