7.2.1
Modification of parameter "acceleration /
deceleration ramp"
The burner leaves the factory with the parameters 522 (acceler-
ation) and 523 (deceleration) already set.
If the operator needs to modify them, proceed as follows:
Access the Parameters Level referring to "Access procedure
with password" on page 40
Using the "+" key select the parameters group 500:
Using the "+" key select the parameters group 522 (accelera-
tion):
press the "info" key to change parameter 522.
The set value must be greater than at least 20% of the parame-
ter "ACCELERATION RAMP" of the Inverter.
Example:
522 at 12s ----> Inverter parameter at 10s
522 at 10s ----> Inverter parameter at 8s
WARNING
P
/reset
With the key "+"
Select the parameter 523 (deceleration):
press the "info" key to change parameter 523.
The set value must be greater than at least 20% of the parame-
ter "DECELERATION RAMP" of the Inverter.
Example:
523 at 12s ----> Inverter parameter at 10s
523 at 10s ----> Inverter parameter at 8s
WARNING
P
/reset