4.2
Operating and setting
Qc1103™
4.2.1

Starting

– Switch on the battery switch, if applicable.
– Turn starter switch S20 to position I (ON) to
power up the Qc1103™ controller.
– Switch off circuit breaker Q1.
– Select the desired operating mode on the
Qc1103™ controller (see chapter "Running
modes" on page 32 for the possible selections).
– To start-up the generator in MANUAL mode:
Press the MAN push button on the Qc1103™
controller to activate MANUAL mode.
Use the START button to start-up the
generator.
The unit will start.
In cold conditions the unit might not start from
the first attempt. The controller will make 3
start attempts.
Allow the generator to start-up till voltage and
frequency are OK (
Hz/V ok
Switch on circuit breaker Q1.
– To start-up the generator in AUTO mode:
Press the AUTO push button on the Qc1103™
controller to activate AUTO mode.
Switch on circuit breaker Q1.
The unit will start automatically at a start
command (e.g. a remote start signal or set
timer).
In cold conditions the unit might not start from
the first attempt. The controller will take 3
start attempts.
4.2.2

During operation

Regularly carry out following checks:
– Check the controller display for normal readings.
!
– Check for leakage of oil, fuel or coolant.
!
– Check that the voltage between the phases is
identical and that the rated current is not
exceeded.
– When single-phase loads are connected to the
generator output terminals, keep all loads well-
lights up).
balanced.
– If circuit breakers have tripped during operation,
switch off the load and stop the generator. Check
and, if necessary, decrease the load.
!
Avoid to let the engine run out of
fuel. If it happened, priming will
speed up the starting.
Avoid
long
low-load
periods
(< 30%). In this case, an output
drop and higher oil consumption of
the engine could occur. Refer to
'Preventing low loads'.
The generator's doors may only
remain opened for short periods
during operation, to carry out
checks for example.
- 25 -
4.2.3

Stopping

– When in MANUAL mode:
Switch off the load.
Switch off circuit breaker Q1.
Press the STOP button to stop the generator
immediately after cooldown.
– When in AUTO mode:
Switch off the load.
The engine will stop when a stop command
(e.g. a remote start/stop signal or set timer) is
given.
– Turn starter switch S20 in position O (OFF) to
shut down the voltage supply towards the
Qc1103™ controller.
– Lock all doors to avoid unauthorized access.