Testing Functionality By Secondary Injection; Testing Disturbance Report; Introduction; Disturbance Report Settings - Hitachi Relion SAM600 Commissioning Manual

Switchgear control unit
Table of Contents

Advertisement

1MRK511447-UEN Rev. E
Section 9
9.1

Testing disturbance report

9.1.1

Introduction

The following sub-functions are included in the disturbance report function:
Disturbance recorder
Event list
Event recorder
If the disturbance report is set on, then its sub-functions are also set up and so it is not possible to
only switch these sub-functions off. The disturbance report function is switched off (parameter
Operation = Off) in PCM600.
9.1.2

Disturbance report settings

When the IED is in test mode, the disturbance report can be made active or inactive. If the
disturbance recorder is turned on during test mode, recordings will be made. When test mode is
switched off all recordings made during the test session are cleared.
To locate disturbance recorder in PCM600,
1.
Open the Disturbance Handling tool for the IED in the plant structure in PCM600
2.
Right-click and select Read Recordings Information.
9.1.3

Disturbance recorder (DR)

A Manual Trig can be started at any time. This results in a recording of the actual values from all
recorded channels.
The Manual Trig can be started as follows:
1.
Open the Disturbance handling tool for the IED in the plant structure in PCM600.
2.
Right-click and select Execute manual Trig in the window Available recordings in IED.
3.
Read the required recordings from the IED.
4.
Refresh the window Recordings and select a recording.
5.
Right-click and select Create Report or Open With to export the recordings to any disturbance
analyzing tool that can handle COMTRADE formatted files.
Evaluation of the results from the disturbance recording function requires access to a PC either
permanently connected to the IED or temporarily connected to the LHMI service kit. The PCM600
software package must be installed in the PC.
Disturbance upload can be performed by the use of PCM600 or by any third party tool with IEC
61850 protocol. Reports can automatically be generated from PCM600. Disturbance files can be
analyzed by any tool reading COMTRADE formatted disturbance files.
It could be useful to have a printer for hard copies. The correct start criteria and behavior of the
disturbance recording function can be checked when IED protective functions are tested.
When the IED is brought into normal service it is recommended to delete all recordings, made during
commissioning to avoid confusion in future fault analysis.
Switchgear control unit SAM600-IO
Commissioning manual
Testing functionality by secondary
injection
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 9

Testing functionality by secondary injection

M17101-2 v7
M11746-2 v7
M11750-2 v8
45