Section 6
6.1

Overview

The customer specific values for each setting parameter and a configuration file have to be available
before the IED can be set and configured.
Use the configuration tools in PCM600 to verify that the IED has the expected configuration.
Each function included in the IED has several setting parameters, which have to be set in order to
make the IED behave as intended. A factory default value is provided for each parameter.The
Parameter Setting Tool in PCM600 is used when changing setting parameters.
All settings can be written from a PC, either locally or remotely using PCM600. The communication
has to be established before the settings can be written to the IED.
The IED uses a FLASH disk for storing configuration data and process data like counters, object
states, Local/Remote switch position etc. Since FLASH memory is used, measures have been taken
in software to make sure that the FLASH disk is not worn out by too intensive storing of data.
This means, that to be absolutely sure that all data have been saved to FLASH, it is necessary to
leave the IED with auxiliary power connected after all the commissioning is done for at least one hour
after the last commissioning action performed on the IED.
After that time has elapsed, it will be safe to turn the IED off, no data will be lost.
6.2

Supervision of input/output modules

I/O modules configured with PCM600 (BIM, BOM or IOM) are supervised.
I/O modules that are not configured are not supervised.
Each logical I/O module has an error flag that indicates signal or module failure. The error flag is also
set when the physical I/O module of the correct type is not detected in the connected slot.
Switchgear control unit SAM600-IO
Commissioning manual
Configuring the IED and changing
settings
Make sure that the DC supply is not turned off when the IED saves the written
configuration.