6 Maintenance
Clean the boiler passes of the economiser
with a brush. Also clean the optional turbula-
tors. If automatic boiler tube cleaning is being
used, six-monthly cleaning is adequate.
Automatic boiler cleaning (12). Check the
compressed air tank for condensate forma-
tion. Slowly open the drain tap and blow out
the condensate.
Clean the turbulators, also see 6.3.1
Check the condition of the firebricks (27) and
the refractory lining (29)
Complete cleaning of the combustion cham-
ber (29), under the combustion retort (18), the
flue gas fan (including the hub) (6), the cy-
clone inlet (32) and the flue gas recirculation
Lubricate according to the lubrication table
Drive motors: Level control
Screw conveyor drive motors: Level control
Clean the flue gas recovery unit (recirculation)
Clean the O
Check the thermal extinguishing water valve
Check the back fire thermostat
Check the rotary valve or back fire protection
slide
Check the differential pressure gauge
Check the safety temperature limiter
Check the thermal process safeguard
Calibrate the O
running
Check the seals on all doors
Check circulating water, replace if necessary
Cleaning of the flue gas pipes (33) and the
chimney (33) by the chimney sweep in accor-
dance with local regulations. Minimum clean-
ing interval in winter operation: 1x yearly
Minimum cleaning interval in summer/winter
operation: 2x yearly
Underfeed grate UTSP
1.10 en
Maintenance tasks
sensor
2
sensor when the system is
2
X
(X)
2.4.6
Option
X
2.4.1
Option
X
(X)
Option
X
X
2.4.4
6.3
X
6.5.6
X
X
X
Option
X
6.5.2
X
Only have
X
carried out
X
by Schmid
AG energy
X
solutions
X
customer
service
X
X
X
6.5.3
X
4.2.1
X
D-57

Advertisement

Table of Contents
loading

Table of Contents