Victrix Tera V2 24 Plus EU
Gas type
G20
G31
Gas type
G20
Victrix Tera V2 35 Plus EU
Gas type
G20
G31
Gas type
G20
If a Hydrogen ready installation is planned for H
ing to local standards in force) all calibration of the unit must refer to the O
In addition to yearly maintenance, one must also check the energy efficiency of the thermal system, with frequency and proce-
dures that comply with the indications of the technical regulations in force.
When adjusting nominal heat input, if the O
adjustments are required.
In the case of an annual inspection of the device, the max CO must be less than 700 ppm (0% O
device requires maintenance/repair.
86
CO
to nominal Q.
2
9,2 (9,1 ÷ 9,5) %
10,2 (10,0 ÷ 10,4) %
O
at Nominal Q.
2
4,4 (4,6 ÷ 3,9) %
CO
to nominal Q.
2
9,0 (8,9 ÷ 9,3) %
10,2 (10,1 ÷ 10,4) %
O
at Nominal Q.
2
4,8 (5,0 ÷ 4,2) %
values are not reached with the gas flow regulator completely open, no further
2
CO
to ignition Q.
2
9,1 (9,0 ÷ 9,4) %
10,2 (10,0 ÷ 10,4) %
O
at Ignition Q.
2
4,6 (4,8 ÷ 4,1) %
CO
to ignition Q.
2
9,0 (8,9 ÷ 9,3) %
10,2 (10,0 ÷ 10,4) %
O
at Ignition Q.
2
4,8 (5,0 ÷ 4,2) %
percentages up to 20%, (referring to the gas distributed in the network accord-
2
values in the table above.
2
CO
to minimum Q.
2
8,5 (8,3 ÷ 8,7) %
9,7 (9,5 ÷ 9,9) %
O
at Minimum Q.
2
5,7 (6,0 ÷ 5,3) %
CO
to minimum Q.
2
8,5 (8,2 ÷ 8,6) %
9,6 (9,4 ÷ 9,8) %
O
at Minimum Q.
2
5,7 (6,2 ÷ 5,5) %
). If the CO value is higher, the
2