Electrical Connection
• Cable entry of inverter
A conduit fitting or cable gland must be used when wiring connection. The cable is
routed from the right side of inverter.
A
C
B
D
Item
Type of Cable Entry
A
Conduit plug for AC connection
B
Conduit plug for communication connection
C
Conduit plugs for PV connection
D
Conduit plugs for PV connection

6.2 Power Connection

Ÿ
General steps of connecting electrical wirings to terminals
Step 1: Choose the appropriate wire according to the specific connection.
Step 2: Remove 0.47 in / 12 mm of insulation from the end of DC wire and the AC
wire.
Step 3: Insert the end of wires into the Cord End Terminal, and then use the
crimping tool to crimp the Cord End Terminal tightly (the shape will be square).
Step 4: Use the slot screwdriver to compress the orange button of the terminals.
Then insert stripped wires into the terminal and ensure that all conductor strands
are captured in the terminal.
Step 5: Loosen the slot screwdriver.
For the specific requirement of power cable, please refer to section 6.1 "Overview
of All Electrical Wiring Methods".
42
0.47 in / 12 mm
Wirings
Strip Length
Conduit
AC wire connection
DC wire connection
Electrical Connection
43

Advertisement

Table of Contents