1.3 Location and Mounting

1.3.1

Location Factors

The generator set MUST be mounted on a non-combustible surface. The preferred method is to mount the generator set at
ground level on a concrete pad. The concrete pad or other non-combustible mounting surface must cover the entire bottom of
the generator base/skid to ensure proper air flow through the enclosure.
For above-ground installations, including roof installations, weight considerations are especially important. The building engineer
must determine whether the structure can support the weight of the generator set.
The location of the generator set must:
Support the weight of the generator set and related equipment such as batteries, radiators, and mounting pad(s). Keep
in mind that the mounting pad weight may exceed the weight of the generator set.
Meet applicable fire rating and other national, state, and local codes and standards.
Minimize the risk that people will come into contact with hot generator set surfaces.
Position the generator set over a noncombustible surface. DO NOT allow accumulation of combustible materials under
or around the generator set.
Allow the use of flexible sections of fuel pipe and conduit to isolate generator set vibration, preventing breakage and
reducing noise.
Not be subject to flooding.
Allow safe direction of engine exhaust as noted on the generator set dimension drawing. Do not locate the generator
set near patios, decks, play areas, or animal shelters.
Provide clearance for cooling air flow and access for service. See Figure 6 and the dimension drawing for required
minimum clearances from obstructions and combustible materials.
Minimize the risk of public or unauthorized access.
DO NOT locate the generator set near patios, decks, play areas, or animal shelters. Keep items such as lawn furniture, toys,
sports equipment, and all combustible materials away from the generator set exhaust outlet.
Remind family members, children, and visitors to use caution near the generator set. Generator sets connected to automatic
transfer switches start automatically during exercise periods and power outages. Some generator set components become
hot when the generator set is running and remain hot for a time after the generator set shuts down.
Service Side
Figure 6
Air Intake and Exhaust
TP-7203
4/23
Notice
GM86793
19