Dc/dc converter units
Hide thumbs Also See for ACS880-1607LC:
Table of Contents

Advertisement

Tasks
WARNING!
When you connect voltage to the supply unit, the DC busbars and the converters connected
to the DC bus will become energized.
WARNING!
Converter units with a DC switch-disconnector: Some types of converter modules can be
energized through a charging circuit even if the DC switch-disconnector is open or the DC
fuses are removed.
Converter units without a DC switch-disconnector: If the converter unit only has DC fuses
without a switch fuse, all the converter units with the DC fuses in position will be energized
when the main breaker/contactor closes. To prevent this, remove the fuses from the con-
verter units which are to remain de-energized before you connect the voltage. Do not install
or remove DC fuses when the main breaker/contactor of the supply unit is closed (DC
busbars are energized).
If the drive is equipped with a main switch-disconnector (option +F253): Close the main discon-
necting device of the drive system.
Close the auxiliary voltage switch [Q21] of the drive supply unit. The converter control unit will
be powered.
Do not close the main circuit breaker [Q1] (option +F255) or the main contactor [Q2] (option
+F250) of the drive supply unit! You must not energize the drive DC bus at this time.
Setting the parameters
Set the DC/DC converter parameters. Refer to chapter Start-up in
program firmware manual (3AXD50000024671
Charging the DC/DC converter and connecting voltage to the converter
Make sure that the energy storage disconnecting device is open.
WARNING!
Always keep the energy storage disconnected from DC/DC converter until the DC/DC
converter is charged.
Start the supply unit and close the main contactor [Q2] (option +F250) or the main circuit
breaker [Q1] (option +F255) of the drive supply unit.
Power up and charge the DC/DC converter:
DC/DC converter with the DC switch-disconnector [Q11] (option +F286):
1. Close the DC/DC converter charging switch [Q10.x]. The DC/DC converter disconnected in-
dicator light [P12.x] goes off.
2. After the Charging OK indicator light [P11.x] comes on, close the DC switch-disconnector
[Q11].
3. Open the DC/DC converter charging switch [Q10.x].
Note: The charging switch must be open before you can start the DC/DC converter.
DC/DC converter without DC switch-disconnector (without option +F286):
1. Start the supply unit and close the main contactor [Q2] (option +F250) or the main breaker
[Q1] (option +F255) of the drive supply unit. The DC/DC converter is energized and gets
charged.
Connecting the energy storage to the DC/DC converter
Set parameter 120.12 Run enable 1 to Off. This makes sure that the DC/DC converter does not
start automatically or unexpectedly after you connect the energy storage.
Set the control panel to local control mode with the Loc/Rem key.
Make sure that the energy storage voltage is less than the drive DC link voltage.
WARNING!
Do not close the energy storage disconnecting device if the DC/DC converter is not con-
nected to the drive DC link or not ready to use.
Close the energy storage disconnecting device. The load disconnected indicator [P13.x] goes off.
DC/DC converter control
[English]).
Start-up 85