Mitsubishi Electric FR-E540-0.4K-EC Instruction Manual page 189

Transistorized inverter
Hide thumbs Also See for FR-E540-0.4K-EC:
Table of Contents

Advertisement

z Checking the inverter and converter modules
<Preparation>
(1)Disconnect the external power supply cables (L
W).
(2)Prepare a meter. (Use 100Ω range.)
<Checking method>
Change the polarity of the meter alternately at the inverter terminals L
U, V, W, + and −, and check for continuity.
Note: 1. Before measurement, check that the smoothing capacitor is discharged.
2. At the time of continuity, the measured value is several to several ten's-of
ohms depending on the number of modules, number of parallel modules,
circuit tester type, etc. If all measured values are almost the same, the
modules are without fault.
<Module device numbers and terminals to be checked>
Tester Polarity
L
1
D1
+
L
2
D2
+
L
3
D3
+
U
TR1
+
V
TR3
+
W
TR5
+
Note: The FR-E520S-0.4K to 2.2K do not have L
Measured Value
+
Discontinuity
L
Continuity
1
+
Discontinuity
L
Continuity
2
+
Discontinuity
L
Continuity
3
+
Discontinuity
U
Continuity
+
Discontinuity
V
Continuity
+
Discontinuity
W
Continuity
Converter module
D1 D2
D3
L
1
L
2
3
D4 D5 D6
PROTECTIVE FUNCTIONS
, L
, L
1
2
Tester Polarity
L
1
D4
L
1
L
2
D5
L
2
L
3
D6
L
3
U
TR4
U
V
TR6
V
W
TR2
W
+
Inverter module
TR1
TR3
TR5
C
TR4
TR6
TR2
, D3 and D6.
3
173
) and motor cables (U, V,
3
, L
, L
,
1
2
3
Measured
Value
Continuity
Discontinuity
Continuity
Discontinuity
Continuity
Discontinuity
Continuity
Discontinuity
Continuity
Discontinuity
Continuity
Discontinuity
U
V
W