LINE
PIC6 DESCRIPTION
1
Quick Test Enable
2
Guide Vane 2 Tested Pos
3
Cond CV (DV Lube Sled)
4
Evap CV (DV Lube Sled)
5
Cond Drain CV
6
Purge Cond SV
7
Purge Comp SV
8
Pumpout SV
9
Drainage SV
10
Purge Rege SV
11
Purge Discharge SV
12
Purge Vacuum Vacuum Pump
13
Purge Compressor
14
Purge Heater
15
Purge Idle Drain SV
16
ECO Liquid Bypass VLV
17
ECO Isolation VLV
18
Condenser Charging VLV
19
Free Cooling VLV
20
Motor Rotation Check
Check State
21
IDLE=0, PreLub=1, Rotat=2, PosLub=3, End=4
LEGEND
RO — Read Only
RW — Read/Write
*Default value is shown only if configurable in this table.
Quick Test Menu
19DV Quick Test
CCN NAME
QCK_TEST
Q_GV2POS
Q_CONDSV
Q_EVAPSV
Q_PRELUB
Q_CDPSV
Q_CMPSV
Q_POPSV
Q_DROPR
Q_RGPSV
Q_DCPSV
Q_PVPSV
Q_PCPSV
Q_PHPSV
Q_IDLE
Q_ECBP
Q_ECONIV
Q_CONDCV
Q_FCMODE
Q_MRC
DISABLE/ENABLE
Q_MRC_ST
65
DEFAULT
RANGE
VALUE*
0 to 1
0
0 to 100
0
OFF/ON
OFF
OFF/ON
OFF
OFF/ON
OFF
OFF/ON
OFF
OFF/ON
OFF
OFF/ON
OFF
OFF/ON
OFF
OFF/ON
OFF
OFF/ON
OFF
OFF/ON
OFF
OFF/ON
OFF
OFF/ON
OFF
OFF/ON
OFF
OFF/ON
OFF
OFF/ON
ON
OFF/ON
OFF
OFF/ON
OFF
DISABLE
0 to 4
UNIT
READ/WRITE
RW
%
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RO

Advertisement