APPENDIX A — PIC6 SCREEN AND TABLE STRUCTURE (CONT)
CCN TABLE NAME: CONF_OPT
PIC6 PATH: Main Menu  Configuration Menu  Option
LINE
PIC6 DESCRIPTION
1
Auto Restart Option
2
Swift Restart Option
3
Gas Torque Factor
4
Guide Vane/SRD Factor
5
Power Recovery Timeout
6
Common Sensor Option
EC/HG Valve Option
7
0 = No, 1= Cont
2 = On/Off, 3 = 4-20 mA
EC/HG Selection
8
0 = Disable, 1 = Surge
2 = Low Load, 3 = Comb
9
EC/HG VLV Open IGV1 Position
10
EC/HG VLV Close IGV1 Position
11
EC/HG VLV Off DT for Low Load
12
EC/HG VLV On DT for Low Load
13
EC/HG VLV Low Load DB
14
Head Pres Valve Option
15
Head Pres Delta P 0%
16
Head Pres Delta P 100%
17
Head Pressure Min Output
18
Head Pressure Deadband
19
Tower Fan High set point
20
Refrigerant Leak Option
21
Refrig Leakage Alarm mA
22
Customer Alert Option
23
Ice Build Option
24
Ice Build Recycle
Ice Build Termin Source
25
0 = Temp, 1 = Contact, 2 = Both
26
Evap Liquid Temp Opt
Evap App Calc Selection
27
Sat Temp = 0, Ref Temp = 1
CCN TABLE NAME: CONFOPT2
PIC6 PATH: Main Menu  Configuration Menu  Option 2
LINE
PIC6 DESCRIPTION
1
IOB4 Option
2
Free Cooling Option
Water Pressure Option (0=No, 1= WTR
3
Flow PD TRD, 2=WTR Flow PD TRM)
Water Pres Drop @ 20 mA
Water Flow Measurement (0=No,
4
1=WTR Flow MTR, 2=WTR Flow PD)
Water Flow at 4mA
Water Flow at 20mA
Evap Flow Rate Baseline
Evap Pres Drop Baseline
Cond Flow Rate Baseline
Cond Flow Rate Baseline
Water Flow Determination (0=Sat Temp,
5
1=Flow Switch, 2=WTR Flow PD)
6
Marine Option
LEGEND
RW — Read/Write
*Default value is shown only if configurable in this table.
Option
CCN NAME
RANGE
astart
DISABLE/ENABLE
swistart
DISABLE/ENABLE
gt_fact
0.25 to 3
gv_srd_f
0.7 to 1.2
pd_tcfg
0 to 60
commsens
DISABLE/ENABLE
hgbp_opt
0 to 3
hgbp_sel
0 to 3
hpop_gv1
0.5 to 10
hgcl_gv1
1.5 to 20
hgb_toff
0.5 to 10.0
hgb_ton
0.5 to 10.0
hgbp_ldb
0.5 to 2.0
hdpv_opt
DISABLE/ENABLE
hdp_0
0 to 85.0
hdp_100
0 to 85.0
hdpv_min
0.0 to 100.0
hdpv_db
0 to 10
tfh_sp
55 to 105
leak_en
DISABLE/ENABLE
exv_opt
4 to 20
cusa_opt
DISABLE/ENABLE
ice_opt
DISABLE/ENABLE
ice_recy
DISABLE/ENABLE
ice_term
0 to 2
evap_ref
DISABLE/ENABLE
evap_ref
0/1
Option 2
CCN NAME
RANGE
iob4_opt
YES/NO
YES/NO
wp_opt
0-2
wpd_20ma
10-40
wfm_opt
0-2
flow4ma
0-12,000
flow20ma
0-12,000
chwf_bas
0-9,000
evpd_bas
0-20
cdwf_bas
0-9,000
cdpd_bas
0-20
fs_opt
0-2
mm_opt
Disable/Enable
57
DEFAULT VALUE*
UNIT
DISABLE
DISABLE
1
0.95
15
min
DISABLE
0
0
5.0
%
10.0
%
4.0
^F
2.0
^F
1.0
^F
DISABLE
25.0
psid
50.0
psid
0.0
%
1
°F
75
DISABLE
20
DISABLE
DISABLE
DISABLE
0
ENABLE
1
DEFAULT VALUE*
UNIT
NO
NO
0
10
psi
0
0
GPM
0
GPM
0
GPM
0
PSI
0
GPM
0
PSI
0
Disable
READ/WRITE
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
READ/WRITE
RW
RW
RW (if wp_opt = 2)
RW (if wfm_opt=1)
RW (if wfm_opt=1)
RW (if wfm_opt=2)
RW (if wfm_opt=2)
RW (if wfm_opt=2)
RW (if wfm_opt=2)
RW
RW