Carrier AquaEdge 19DV Operation And Troubleshooting page 64

Two-stage high-efficiency semi-hermetic centrifugal liquid chillers with pic6 controls
Table of Contents

Advertisement

APPENDIX A — PIC6 SCREEN AND TABLE STRUCTURE (CONT)
Navigation: MAIN MENU  SYSTEM CONFIGURATION MENU DATE/TIME CONFIGURATION
Navigation: MAIN MENU  QUICK TEST
CCN TABLE NAME: QCK_TEST
PIC6 PATH: Main Menu  Quick Test
LINE
PIC6 DESCRIPTION
1
Quick Test Enable
2
Oil/Ref Pump
3
Oil/Ref Pres Test Passed
4
Oil/Ref Pump Delta Press
5
HPR VLV Position
6
Chiller Status (Analog)
7
Chiller Status (Discrete)
8
Guide Vane 1 Pos
9
Guide Vane 1 Actual Pos
10
EC/HC Valve Tested Pos
11
Alarm Output
12
Alert Output
13
Condenser Water Pump
14
Condenser Water Flow
15
Chilled Water Pump
16
Chilled Water Flow
17
Condenser Water Delta T
18
Chilled Water Delta T
19
Liquid Level EXV
20
Free Cooling
21
Low Speed Tower Fan
22
High Speed Tower Fan
23
Shunt Trip Relay
LEGEND
RO — Read Only
RW — Read/Write
Date/Time Configuration
Fig. E — Date/Time Configuration Menu
Quick Test Menu
Quick Test
CCN NAME
QCK_TEST
Q_OILP
OP_PASS
OIL_PDQ
Q_HDP
Q_CHST
Q_RUN_ST
Q_GV1POS
Q_GV1ACT
Q_HGBP_T
Q_ALM
Q_ALE
Q_CDWP
CDW_FLOW
Q_CHWP
CHW_FLOW
CDW_DT
CHW_DT
Q_LLCEXV
Q_FCMODE
Q_LOWFAN
Q_HIFAN
Q_TRIPR
*Default value is shown only if configurable in this table.
64
DEFAULT
RANGE
VALUE*
0 to 1
0
0 to 1
0
0 to 1
0 to 100
0
4 to 20
4
OFF/ON
OFF
0 to 100
0
0 to 100
0
OFF/ON
OFF
OFF/ON
OFF
OFF/ON
OFF
YES/NO
OFF/ON
OFF
YES/NO
–22.2 to 136.1
–22.2 to 136.1
0 to 100
0
OFF/ON
OFF
OFF/ON
OFF
OFF/ON
OFF
OFF/ON
OFF
UNIT
READ/WRITE
RW
RW
RO
psi
RO
%
RW
mA
RW
RW
%
RW
%
RO
%
RW
RW
RW
RW
RO
RW
RO
F
RO
F
RO
%
RW
RW
RW
RW
RW