Download Print this page
Bender ISOSCAN EDS440 Connection Manual
Bender ISOSCAN EDS440 Connection Manual

Bender ISOSCAN EDS440 Connection Manual

Hide thumbs Also See for ISOSCAN EDS440:

Advertisement

Quick Links

ISOSCAN® EDS440 and EDS441
Insulation fault locator to locate insulation faults in
ungrounded DC, AC and three-phase power supplies
EDS44x_D00201_11_D_XXEN/11.2023

Advertisement

loading

Summary of Contents for Bender ISOSCAN EDS440

  • Page 1 ISOSCAN® EDS440 and EDS441 Insulation fault locator to locate insulation faults in ungrounded DC, AC and three-phase power supplies EDS44x_D00201_11_D_XXEN/11.2023...
  • Page 2 ISOSCAN® EDS440 and EDS441 Insulation fault locator to locate insulation faults in ungrounded DC, AC and three-phase power supplies Intended use The insulation fault locators ISOSCAN® EDS440 and EDS441 are used to locate insulation faults in unearthed DC, AC and three-phase power supply systems (IT systems). Depending on the locating current injector, AC and three-phase systems can be monitored within the range from AC 42 to 1000 V;...
  • Page 3 ISOSCAN® EDS440 and EDS441 Operating principle of the EDS system When an insulation monitoring device detects an insulation fault, The locating current is generated by the locating current injector. it starts the insulation fault location. It is limited in amplitude and time. The amplitude depends on the size of the existing insulation fault and the system voltage.
  • Page 4 ISOSCAN® EDS440 and EDS441 Display elements EDS44…-S Operating and display elements EDS44…-L TEST CHANNELS / ADDR. COM/ADDR. RESET SERVICE Addr. Mode ALARM ∆ ADDR. >3s ALARM ∆ Status LED Status LEDs Flashes: Starting process; hourly transformer connection test Flashes: Starting process; hourly transformer connection test Lights up: operational Lights up: operational...
  • Page 5 ISOSCAN® EDS440 and EDS441 Connection to the voltage supply BS bus termination L1/+ L2/– 23 24 13 14 9 10 11 12 A1 A2 A1/+ A2/– U s = AC/DC 24...240 V Voltage supply back-up fuse Activating a terminating resistor to define the first and the last device in the bus system.
  • Page 6 ISOSCAN® EDS440 and EDS441 Connection of CTAC… series measuring current transformers Connection of measuring current transformer CTBC… to EDS441-LAB-4 For insulation fault location, the measuring current transformers of the CTAC… series are used. CTAC 1 CTAC 2 Type A CTBC… CTUB102 A1/+ A2/- S1(k) S2(l)
  • Page 7 ISOSCAN® EDS440 and EDS441 Connection to a 3(N)AC system A1/+ A2/- L1/+ L3/- A1/+ A2/- A1/+ A2/- A1/+ A2/- L1/+ L3/- KE E iso685 ISOMETER ® EDS440 ΔL Δn ISOSCAN ® 13 14 23 24 11 12 14 21 22 24 l1 l2 A B l1 l2 l3 A B iso685-D-P...
  • Page 8 ISOSCAN® EDS440 and EDS441 Connection to a DC system L– A1/+ A2/- L1/+ L3/- A1/+ A2/- A1/+ A2/- A1/+ A2/- L1/+ L3/- KE E iso685 ISOMETER ® EDS440 ΔL Δn ISOSCAN ® 13 14 23 24 11 12 14 21 22 24 l1 l2 A B l1 l2 l3 A B iso685-D-P...
  • Page 9 ISOSCAN® EDS440 and EDS441 Connection to an AC system A1/+ A2/- L1/+ L3/- A1/+ A2/- A1/+ A2/- A1/+ A2/- L1/+ L3/- KE E iso685 ISOMETER ® EDS440 ΔL Δn ISOSCAN ® 13 14 23 24 11 12 14 21 22 24 l1 l2 A B l1 l2 l3 A B iso685-D-P...
  • Page 10 ISOSCAN® EDS440 and EDS441 Connection example: ISOMETER® iso685-D-P, EDS440-S, IOM441-S and EDS440-L A1/+ A2/- L1/+ L3/- A1/+ A2/- A1/+ A2/- L1/+ L3/- KE E A1/+ A2/- iso685 ISOMETER ® EDS440 IOM441 EDS440 ΔL Δn ΔL Δn ISOSCAN ISOSCAN ® ® 11 12 14 21 22 24 13 14...
  • Page 11 ISOSCAN® EDS440 and EDS441 Technical data ISOSCAN® EDS440 and EDS441 Insulation coordination acc. to IEC 60664-1/IEC 60664-3 Response values EDS440 EDS441 Definitions Response value for insulation fault 2…10 mA 0.2…1 mA Supply circuit (IC1) A1, A2 location (I Output circuit 1 (IC2) 13, 14 Relative uncertainty (I ±30 %,...
  • Page 12 ISOSCAN® EDS440 and EDS441 Measuring ranges, insulation fault location I Interfaces Interface/protocol RS-485 | BS-Bus | Modbus RTU Rated frequency range DC, 16.7…1000 Hz Data rate BS bus 9.6 kBd Measuring range, insulation fault 1.5…50 mA Data rate Modbus RTU 9.6 | 19.2 | 37.4 | 57.6 | 115 kBd location (I ) EDS440...
  • Page 13 ISOSCAN® EDS440 and EDS441 Connection “W” option data deviating from the standard version Devices with the suffix “W” feature increased shock and vibration Screw-type terminals resistance. The electronics is covered with a special varnish to Tightening torque 0.5…0.6 Nm (5…7 lb-in) provide increased protection against mechanical stress and Conductor sizes AWG 24-12...
  • Page 14 Observe the applicable national and international standards. EU declaration of conformity The EDS44… series meets the device standards: Hereby, Bender GmbH & Co. KG declares that the device covered • DIN VDE 0100-410 (VDE 0100-410) by the Radio Directive complies with Directive 2014/53/EU. The •...
  • Page 15 ISOSCAN® EDS440 and EDS441 Accessories Alternative measuring current transformers from the Bender program Description Art. no. Type Dimensions / inter- Design type Art. no. EDS440/441 mechanical accessories comprising: B91080903 nal diameter in terminal cover and 2 mounting clips (scope of delivery)
  • Page 16 B78120021 CTBC20P CTAC35/01 ø35 circular B98110008 CTUB102- ø35 circular B78120023 CTBC35P Alternative measuring current transformers from the Bender program CTUB102- ø60 circular B78120025 CTBC60P Type Dimensions / inter- Design type Art. no. nal diameter in Measuring current transformers for EDS440-LAF CTAS50/01 ø50...