Walktesting Groups; Duration And Termination - Siemens FCM2041-U3 Interface Manual

Cerberus pro modular
Hide thumbs Also See for FCM2041-U3:
Table of Contents

Advertisement

CHAPTER 3 |

Walktesting Groups

Duration And Termination

The Walktest status screen indicates the time remaining in Walktest. The time is
indicated as HH:MM (hours:minutes).
Menu:Walktest
PHY:FireFinder@1, DLC@1
AT: FireFinder@1, DLC@1
WALKTEST:
ENABLED
SETTINGS:
No Bells
TIME REMAINING (HH:MM):4:00
Cancel
Settings
Figure 3-30
Walktest Enabled Screen
Only one Walktest may be active on a system at any one time.
When a Walktest is performed on a Geographic group, all walktestable devices in
the group are placed in walktest. All non-walktestable devices are not affected.
The Group Bells mode is available when walktesting groups. When this option is
selected, all applicable ZIC/voice devices in that group will activate. This will enable
the technician to walktest all devices on a floor, and have only the audibles on that
floor activate, provided the system is configured in floor-specific groups.
Once enabled, the Walktest remains in effect for four hours. At any time during the
Walktest, the user may extend the Walktest by pressing the Extend soft key on the
Walktest status screen. This will reset the Time Remaining to four hours. The
Walktest may be extended up to four times.
The user may cancel the walktest at any time by pressing the Disable soft key on the
Walktest status screen. After returning to the Alert Screen, Acknowledge the
"Walktest Activated" trouble and reset the panel.
FCM2041-U3 OPERATOR INTERFACE MANUAL
WALKTEST
Disable
Extend
MAINTENANCE MODE
3-19

Advertisement

Table of Contents
loading

Table of Contents