CHAPTER 1 |
Single Point of Control
When configured for Single Point of Control in Zeus (version 12 and above), if a
Modular node is granted control of the network, only that node will have Voice, Fire,
and MNS control over the entire network. Control is managed by global Voice
Command stations associated with the node in control via its Request/Grant/Deny
switches. Any Global OI in the network that does not have control via one of its Voice
Command Stations will behave as a Display-Only Global OI without local control. The
FCM2041-U3 will indicate when the node has global control, as follows:
SUP
001
Figure 1-11
Node X in Control
FCM2041-U3 OPERATOR INTERFACE MANUAL
BIDG
TBL
MNST
OTH
000
001
000
000
Node X in Control
BASIC OPERATION
1-15