Final Calibration Of The Pressure Switches; Air Pressure Switch; Maximum Gas Pressure Switch; Minimum Gas Pressure Switch - Riello RLS 70/EV Installation, Use And Maintenance Instructions

Dual fuel light oil/gas burners
Table of Contents

Advertisement

5.7

Final calibration of the pressure switches

5.7.1

Air pressure switch

The air pressure switch (Fig. 47) is connected in differential and is
activated by both the negative pressure of the air intake and the air
pressure from the fan.
Adjust the air pressure switch (Fig. 46) after having performed all
other burner adjustments with the air pressure switch set to the
min. of the scale.
With the burner operating at low fire, adjust the pressure switch by
slowly turning the relative knob clockwise until the burner locks out.
Then turn the knob counter-clockwise about 20% of the set point
and start-up the burner again to ensure the set point is correct.
If the burner locks out again, turn the knob counter-clockwise a little
bit more.
5.7.2

Maximum gas pressure switch

Adjust the maximum gas pressure switch (Fig. 48) after having per-
formed all other burner adjustments with the maximum gas pres-
sure switch set to the end of the scale.
With the burner operating at MAX output, reduce the adjustment
pressure by slowly turning the adjustment dial anticlockwise until
the burner locks out.
Then turn the dial clockwise by 0.8" WC and repeat burner firing.
If the burner locks out again, turn the dial again clockwise by
0.4" WC.
5.7.3

Minimum gas pressure switch

Adjust the minimum gas pressure switch (Fig. 49) after having per-
formed all the other burner adjustments with the pressure switch
set at the start of the scale.
With the burner operating at MAX output, increase adjustment
pressure by slowly turning the relative dial clockwise until the burn-
er locks out.
Then turn the dial anti-clockwise by 0.8" WC and repeat burner
starting to ensure it is uniform.
If the burner locks out again, turn the dial anti-clockwise again by
0.4" WC.
Start-up, calibration and operation of the burner
35
GB
D3854
20066617
D9272
D9290
Fig. 46
Fig. 47
Fig. 48
Fig. 49
20036932

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rls 100/evC9335700C9335710C933570120065636

Table of Contents