Unit Inspection - Trane Voyager TS 150F Series Installation, Operation And Maintenance Manual

Packaged rooftop air conditioners
Table of Contents

Advertisement

General Information
Thermostat (BAYSTAT151)
This thermostat is a single-stage 1 heat/1 cool, auto-
changeover digital display thermostat. It is a non-
programmable, wall-mounted thermostat.
Thermostat (BAYSTAT155)
This thermostat is a multi-stage 3 heat/2 cool, auto
changeover digital display thermostat. It is a non-
programmable, wall-mounted thermostat, and it can be
used for Economizer Operation.
Smoke Detector Sensor (Optional)
This sensor is only applicable on units equipped with a
RTOM. It provides high limit "shutdown" of the unit and
requires a manual reset. The sensor is used to detect
smoke due to fire in the air conditioning or ventilation
ducts.
Notes:
The supply and return air smoke detectors are
designed to shut off the unit if smoke is sensed in the
supply air stream or return air stream. This function is
performed by sampling the airflow entering the unit at
the return air opening. Follow the instructions
provided below to assure that the airflow through the
unit is sufficient for adequate sampling. Failure to
follow these instructions will prevent the smoke
detectors from performing it's design function.
Airflow through the unit is affected by the amount of
dirt and debris accumulated on the indoor coil and
filters. To insure that airflow through the unit is
adequate for proper sampling by the return air smoke
detector, complete adherence to the maintenance
procedures, including recommended intervals
between filter changes, and coil cleaning is required.
Periodic checks and maintenance procedures must be
performed on the smoke detector to insure that it will
function properly. For detailed instructions concerning
these checks and procedures, refer to the appropriate
section(s) of the smoke detector Installation and
Maintenance Instructions provided with the literature
package for this unit.
In order for the supply air smoke detector or return air
smoke detector to properly sense smoke in the supply air
stream or return air stream, the air velocity entering the
smoke detector unit must be between 500 and 4000 feet
per minute.
Equipment covered in this manual will develop an airflow
velocity that falls within these limits over the entire airflow
range specified in the evaporator fan performance tables.
There are certain models, however, if operated at low
airflow, will not develop an airflow velocity that falls within
the required 500 to 4000 feet per minute range. For these
models, the design airflow shall be greater than or equal
to the minimum cfm specified in the table provided below.
10
Failure to follow these instructions will prevent the smoke
detector from performing its design function.
Un i t M o d e l
M i n i m u m A l l o w a b l e A i r f l o w w i t h
N u m b e r
Ret u r n A i r Sm o k e D e t e ct o r
THD180
Wall Mounted Relative Humidity Sensor
(BAYSENS036*)
Field installed, wall mounted humidity sensor is used to
control activation of the hot gas reheat dehumidification
option.
Humidity set points can be selected for relative humidity
levels between 40 percent and 60 percent by adjusting the
DEHUMID setting on the ReliaTel Options Module; see
"RTOM—ReliaTel™ Options Module (Optional), " p.
Duct Mounted Relative Humidity Sensor
(BAYSENS037*)
Field installed, duct mounted humidity sensor is used to
control activation of the hot gas reheat dehumidification
option.
Humidity set points can be selected for relative humidity
levels between 40 percent and 60 percent by adjusting the
DEHUMID setting on the ReliaTel Options Module; see
"RTOM—ReliaTel™ Options Module (Optional), " p.

Unit Inspection

As soon as the unit arrives at the job site:
Verify that the nameplate data matches the data on the
sales order and bill of lading (including electrical data).
Verify that the power supply complies with the unit
nameplate specifications.
Visually inspect the exterior of the unit, including the
roof, for signs of shipping damage.
Visually inspect the internal components for shipping
damage as soon as possible after delivery and before
it is stored. Do not walk on the sheet metal base pans.
If concealed damage is discovered, notify the carrier's
terminal of damage immediately by phone and by
mail. Concealed damage must be reported within 15
days.
– Request an immediate joint inspection of the
damage by the carrier and the consignee.
– Do not remove damaged material from the
receiving location.
– Take photos of the damage, if possible. The owner
must provide reasonable evidence that the damage
did not occur after delivery.
Notify the appropriate sales representative before
installing or repairing a damaged unit.
5300 cfm
7.
7.
RT-SVX25G-EN