(3) Cables for CC-Link IE Field Network
Note the following when using cables for CC-Link IE Field Network.
• Be sure to use the cables for the CC-Link IE Field Network
(SC-E5EW-SM, manufactured by Mitsubishi Electric
System & Service Co., Ltd.).
• Shielded cables should be used for the CC-Link IE Field
Network. Strip a part of the jacket as shown below and
ground the exposed shield in the largest possible area.
• Use shielded cables for external wiring and ground the
shields of the external wiring cables to the control panel with
the AD75CK-type cable clamp (Mitsubishi). (Ground the
shield of the CC-Link IE Field Network cable 20cm to 30cm
away from the module.)
Head module
Inside control box
AD75CK
CC-Link IE Field Network cable
Shield
20 to 30cm (7.87 to 11.81 inch)
45